Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateWA
Date of Visit10/05/2018
Technician's NameAdam Hoes
Built Job Number30450
Swarovski in WAcarousel
Test Period3 Monthly
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
Eaton RCD Switchboard 5 x 10 amp, 1 x 20 amp Faulty Eaton N OH&S. RCD's have been recalled. Built to investigate and replace
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Front display lights Front window boxes 3 Swarvoski sign not illuminated N Y TBA Lighting issue
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Schott 7 spot light Display cabinet 2 x lights are faulty N N John, please confirm if repairs are required
Schott 9 spot light Display cabinet 1 x light is faulty N N John, please confirm if repairs are required
Fire Extinguisher Back of house Not compliant, overdue for testing N N Repairs approved by John Cowles 24/05/2018. To be scheduled as soon as possible
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE 2.5kg 04/13 10/13 Green Back of house N
Next Test Due in 3 months10/08/2018
Site Status SelectorStore now fully compliant
Technician's NameAdam Hoes
Store Manager's NameJennifer Grabowski