Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB1
01
R
Y
Y
Y
P
DB1
02
R
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
Yes
Comments
Clean
Fixture draws able to open and close freely?
Yes
Comments
Yes
Locks work on all fixtures?
Yes
Comments
Yes
Is there chips, dents or defects to joinery?
Yes
Comments
There are some visible chips on the low cabinets. Touch up paint would suffice.
Storeroom door is much worse condition. John, please advise if repairs are required.
Is there damage to skirtings?
No
Comments
Ok
General cleanliness of fixtures, ceilings, P.O.S - provide details
Yes
Comments
Ok
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
No
Comments
NA - none onsite
General cleanliness of Façade? - provide details
Yes
Comments
Ok
Lighting operational, (eg logo)?
No
Comments
Logo closer to escalator isn't as bright as the one over the door. John, please advise if repairs are required.
Windows clean?
Yes
Comments
Yes
Door handles clean and tight?
Yes
Comments
Yes
Any issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Exit Lights
Shop floor
-
No Exit Lights installed onsite.
N
Y
TBA
Quote to be sent for approval.
Free standing glass cabinet display
Shop window near storeroom
1
"Swarovski" sign is no illuminated
N
N
TBA
John, please advise if repairs are required.
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
C02
3.5kg
10/2012
11/2012
N/A
Storeroom beside sink
N - recommend testing ASAP.
Confirm how many power points are underneath the window box?
One
Next Test Due in 3 months
23/10/2018
Site Status Selector
Completed but with repairs required
Technician's Name
Matthew Mullins
Store Manager's Name
Lisawati Gan