Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateVIC
Date of Visit27/07/2018
Technician's NameAnthony Zammit
Built Job Number31999
Swarovski Site in VICknox_city
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
2 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auNo
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsYes
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsYes
Lighting operational, (eg logo)?No
Comments

Light failed to illuminate.

Windows clean?Yes
Door handles clean and tight?Yes
Any issues found onsite please take photos and upload hereAny issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Switchboard legend Store room 1 Missing Y N N Created new switchboard legend on site
Switchboard Store room All Circuits No RCD installed N Y TBA Due to age of store, switchboard needs updating and new circuit needs to be run for exit/emergency lights. John please confirm if repairs are required.
Swarovski front sign Front of store 1 Failed to illuminate N N N Store closing for refurbishment on 12/08/2018
Store lights Shop floor 2 Failed to illuminate N N N Store closing for refurbishment on 12/08/2018. Photo of faulty light attached.
36W fluorescent lights Store room 2 Failed to illuminate N N N Store closing for refurbishment on 12/08/2018
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?No
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE Powder 2.5 7-18 07/11 Green Zone storeroom y
Confirm how many power points are underneath the window box?One
Next Test Due in 3 months26/10/2018
Site Status SelectorStore now fully compliant
Technician's NameAnthony Zammit
Store Manager's NameNaomi White