Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateWA
Date of Visit06/08/2018
Technician's NameAdam Hoes
Built Job Number32050
Swarovski in WAbooragoon
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
db 01 1 Y P
3 Y P
5 Y P
7 Y P
9 Y P
11 Y P
13 Y P
15 Y P
17 Y P
19 not rcd not rcd not rcd not rcd
21 blank blank blank blank
23 blank blank blank blank
2 Y P
4 Y P
6 Y P
8 Y P
10 Y P
12 Y P
14 Y P
16 Y P
18 Y P
20 blank blank blank blank
22 blank blank blank blank
24 blank blank blank blank
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
db 01 1 R Y Y Y P
2 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 3 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?Yes
Comments

GENERAL CHIPS ON CABINETS. TOUCH UP IS REQUIRED
SMALL CHIPS ON 5 X VITRINES
MULTIPLE CHIPS ON WHITE STAND
EARING SPINNER - CHIPS ON BOTTOM OF THE CABINET

Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsYes
Roller shutters in working order and clean?Yes
Comments

STORE DOES NOT HAVE ROLLER SHUTTERS

General cleanliness of Façade? - provide detailsYes
Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
1 X SHOP LIGHT SHOP FLOOR 1 1X 35W/930 CDM-TM MINI PGJ5 LAMP Y N N
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Cabinets Showroom Chips on cabinets, touch up is required N N John, please confirm if repairs are required
Vitrines Showroom Small chips on 5 x vitrines N N John, please confirm if repairs are required
White Stand Showroom Multiple chips on stand N N John, please confirm if repairs are required
Earing Spinner Showroom Chips on bottom of the cabinet N N John, please confirm if repairs are required
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE POWER 4.6KG APRIL/2018 01/2018 GREEN BACK OF HOUSE Y
Confirm how many power points are underneath the window box?One
Next Test Due in 3 months06/11/2018
Site Status SelectorStore now fully compliant
Technician's NameADAM HOES
Store Manager's NameWIJAYA HANNY