Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateSA
Date of Visit08/08/2018
Technician's NameDaniel Moio
Built Job Number32049
Swarovski Site in SAmarion
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
unlabeled 1 Y P
2 Y P
3 Y P
4 Y P
6 Y P
8 Y P
10 Y P
12 Y P
14 Y P
16 Y P
18 Y P
20 Y P
22 Y P
24 Y P
26 Y P
28 Y P
30 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsYes
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsYes
Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency lighting Switchboard 1 No emergency lighting test facility N Y TBA
LED strip light Necklaces 1 Broken light N N TBA 9 light strip. John, please confirm if repairs are required
Spotlight Centre of store 1 No illumination N Y TBA Replaced globe a few months ago, has blown since. Light appears to be faulty and causing globes to blow. Recommend LED upgrade
Switchboard Store room 1 Not compliant N Y TBA Switchboard needs a clearance zone. Data rack needs to be moved to make it compliant
General Works Checklist
  • Inspect all furniture and fittings for visible damage
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Fire Extinguisher Store room Expired N N Technician to attend and replace. Approval received by John Cowles 31/08/2018
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE 2.5kg March 2012 05/2011 Green Store room N
Confirm how many power points are underneath the window box?One
Next Test Due in 3 months08/11/2018
Site Status SelectorCompleted but with repairs required
Technician's NameDanny Moio
Store Manager's NameAngela Clarke