| Which Company are you working for? | Built Electrical QLD |
|---|
| Which Trade are you working for? | Electrical |
|---|
| State | QLD |
|---|
| Date of Visit | 14/08/2018 |
|---|
| Technician's Name | Andrew Farmer |
|---|
| Built Job Number | 32094 |
|---|
| Swarovski Site in QLD | robina |
|---|
| Test Period | 6 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| RCD Details (6 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| 1 |
2 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
- Report any failures and provide costing to rectify (where applicable)
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| 1 |
1 |
|
Y |
Y |
Y |
P |
|
|
|
| 2 |
2 |
|
Y |
Y |
Y |
P |
|
|
|
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| 1 |
1 |
Y |
Y |
Y |
P |
|
|
|
| 2 |
2 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au | Yes |
|---|
| If Yes, please upload all copies of legends here... (Limit of 6 megabytes total) |  |
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| Paint & surfaces are clean? | Yes |
|---|
| Fixture draws able to open and close freely? | Yes |
|---|
| Locks work on all fixtures? | No |
|---|
| Comments | The lock for the glass cabinet that is the first cabinet on the left as you walk in the store is intermittently difficult to close.
|
|---|
| Is there chips, dents or defects to joinery? | Yes |
|---|
| Comments | Upper skirting below the second cabnet on the left has two small chunks missing.
|
|---|
| Is there damage to skirtings? | Yes |
|---|
| Comments | See above.
|
|---|
| General cleanliness of fixtures, ceilings, P.O.S - provide details | Yes |
|---|
| Any issues found onsite please take photos and upload here |  |
|---|
| Roller shutters in working order and clean? | Yes |
|---|
| General cleanliness of Façade? - provide details | Yes |
|---|
| Lighting operational, (eg logo)? | Yes |
|---|
| Windows clean? | Yes |
|---|
| Door handles clean and tight? | Yes |
|---|
| General Works Checklist | - Inspect all furniture and fittings for visible damage
- Inspect all walls, ceilings, skirtings and floors for visible damage
- Inspect storefront, façade and store LED logo for correct operations and visible damage
- Inspect roller shutter and doors for correct operations and visible damage
- Check fire extinguishers, update compliance tags/labels
|
|---|
| Are there any repairs and additional works required? | Yes |
|---|
| General List of Repairs and additional works required | | Defect Item |
Location of Item |
Details of Problem |
Repaired on Site |
Quote to be Sent |
Comments |
| Locks on Glass Cabinet |
Left hand side near entry |
Lock on cabinet intermittently difficult to close |
N |
N |
John, please advise if repairs are required. |
|
|---|
| Fire Extinguisher Details | | Type (ABE Powder) |
Size (4.5kg) |
Last Test Date |
Manufacture Date |
Pressure Indicator (Green Zone) |
Location In Store |
Compliant (Y/N) |
| ABC powder |
3kg |
06/2018 |
01/2016 |
Green |
Storeroom |
Y |
|
|---|
| Confirm how many power points are underneath the window box? | One |
|---|
| Next Test Due in 3 months | 14/11/2018 |
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Technician's Name | Andrew Farmer |
|---|
| Store Manager's Name | Jan Biles |
|---|
| |
|---|
| |