Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateWA
Date of Visit27/08/2018
Technician's NameAdam Hoes
Built Job Number32050
Swarovski in WAperth
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1 Y P
DB 01 3 Y P
DB 01 5 Y P
DB 01 7 Y P
DB 01 9 Y P
DB 01 11 Y P
DB 01 13 blank blank
DB 01 15 blank blank
DB 01 19 blank blank
DB 01 21 blank blank
DB 01 2 Y P
DB 01 4 Y P
DB 01 6 Y P
DB 01 8 blank blank
DB 01 10 blank blank
DB 01 12 blank blank
DB 01 14 blank blank
DB 01 16 blank blank
DB 01 18 blank blank
DB 01 20 blank blank
DB 01 22 blank blank
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 2 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 1 Y Y Y P
DB 01 3 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?No
Comments

WATCH VITRINE GLASS CABNET LOOSE GLASS FRONT PANEL

Locks work on all fixtures?No
Comments

CRYSTAL CABINET 2 - BOTTOM DRAW LOCK HAS A SNAPPED OFF KEY INSIDE MAY REQUIRE NEW LOCK - LOCK CODE IS 0089

TALL SKINNY CABINET BETWEEN SHOW CASE CABINET LOCK IS MISSING ITS SKINNY NUT RESULTING IN THE LOCK TO BE LOOSE

LOCKING MECHANISM NOT WORKING ON THE STYLING VITRINE GLASS CABINET DRAWS MIDDLE DRAW DOES NOT LOCK

Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsYes
Comments

SWITCH BOARD HAS NO ACCESS AND DOES NOT COMPLY TO AUSTRALIAN STANDARDS RELOCATION REQUIRED

Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?Yes
Comments

N/A

General cleanliness of Façade? - provide detailsYes
Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG ENTIRE STORE 32 ITEMS LAST TESTED 2015 N Y TBA
SWITCHBOARD BOH 1 REQUIRES RELOCATION N Y TBA SWITCHBOARD HAS LIMITED ACCESS AND DOES NOT COMPLY TO AUSTRALIAN STANDARDS. WILL REQUIRE TO BE RELOCATED
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
STYLIN VITRINE SHOP FLOOR MIDDLE DRAW DOES NOT LOCK N N JOHN, PLEASE CONFIRM IF REPAIRS ARE REQUIRED. EMAIL FOR APPROVAL SENT 05/09/2018
TALL SKINNY CABNET SHOP FLOOR MISSING NUT N N JOHN, PLEASE CONFIRM IF REPAIRS ARE REQUIRED. EMAIL FOR APPROVAL SENT 05/09/2018
WATCH VITRINE SHOP FLOOR LOOSE GLASS PANEL N N JOHN, PLEASE CONFIRM IF REPAIRS ARE REQUIRED. EMAIL FOR APPROVAL SENT 05/09/2018
CRYSTAL CABNET 2 SHOP FLOOR BROKEN KEY IN LOCK N N JOHN, PLEASE CONFIRM IF REPAIRS ARE REQUIRED. EMAIL FOR APPROVAL SENT 05/09/2018
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE POWDER 4.3KG JUNE /18 09/16 GREEN BOH Y
Confirm how many power points are underneath the window box?One
Next Test Due in 3 months27/11/2018
Site Status SelectorStore now fully compliant
Technician's NameADAM HOES
Store Manager's NameElaine Barbier