Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateNSW
Date of Visit17/10/2018
Technician's NameMatthew Mullins
Built Job Number34463
Swarovski Site in NSWmid_city
Test Period9 Monthly
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Comments

Clean

Fixture draws able to open and close freely?Yes
Comments

Yes

Locks work on all fixtures?Yes
Comments

Yes

Is there chips, dents or defects to joinery?Yes
Comments

Just general wear and tear

Is there damage to skirtings?Yes
Comments

Just scuffs from general use

General cleanliness of fixtures, ceilings, P.O.S - provide detailsYes
Comments

Clean

Roller shutters in working order and clean?No
Comments

N/A

General cleanliness of Façade? - provide detailsYes
Comments

Very clean

Lighting operational, (eg logo)?Yes
Comments

Illuminated

Windows clean?Yes
Comments

Clean

Door handles clean and tight?Yes
Comments

Solid

ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Material lightbox display In side window 1 LED strip light off Y N N Reconnection was required
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Tall display cabinets All Mirror side panel is pulling away from glass sides of cabinet N N Possible some good quality double sided tape would fix. John, please advise if repairs are required.
Keys Earring spin display Require more keys cut for most displays N N Very few keys for display. John, please advise if repairs are required.
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE 4.5kg 06/2018 04/2017 Green On right wall when entering the storeroom Y
Next Test Due in 3 months17/01/2019
Site Status SelectorStore now fully compliant
Technician's NameMatthew Mullins
Store Manager's NameMayri Mayri