Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly? Tick is present
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
1
R
Y
Y
Y
P
2
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
No
Comments
Expansion joint causing cracking in ceiling, cracks getting worse and would recommend repairing
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
No
Comments
One lock missing in cabinet missing behind counter. Cabinet is empty and being used only for staff’s personal belongings.
Is there chips, dents or defects to joinery?
No
Is there damage to skirtings?
No
General cleanliness of fixtures, ceilings, P.O.S - provide details
Yes
Comments
Good
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Yes
Comments
Good
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
Yes
Are there any repairs and additional works required?
No
General List of Repairs and additional works required
Defect Item
Location of Item
Details of Problem
Repaired on Site
Quote to be Sent
Comments
Ceiling & Wall Cracks
Near expansion joint
Expansion joint causing cracking in ceiling
N
N
Needs to be repaired as wall/ceiling cracks are getting worse
Cabinet lock
Cabinet behind counter
Missing lock
N
N
Manager advised this cabinet is being used only for staff's personal belongings and does not need locking. John please confirm if repairs are required.
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
ABE
2.5
July 18
04/15
Green
BOH
Y
Next Test Due in 3 months
21/04/2019
Site Status Selector
Store now fully compliant
Technician's Name
Gerard O'Connell
Store Manager's Name
Georgia Rogers