Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateNSW
Date of Visit21/01/2019
Technician's NameMorgan Jackson
Built Job Number36431
Swarovski Site in NSWkotara
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (12 Month)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
2068 1 Y 0.0018 0.0011 P
2068 2 Y 0.0015 0.0021 P
2068 3 Y 0.0024 0.0015 P
2068 4 Y 0.0016 0.0011 P
2068 6 Y 0.0016 0.0023 P
2068 7 Y 0.0012 0.0019 P
2068 8 Y 0.0017 0.0023 P
2068 9 Y 0.0021 0.0025 P
2068 10 Y 0.0016 0.0021 P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
2068 None R Y Y Y P
2068 None R Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?No
Comments

Watch table drawers are sticking.
3 drawer Vitrines x 2 - drawers are sticking.
Feature vitrine drawers are sticking.

Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Comments

Good

Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsGood
Comments

Good

Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Downlights Throughout store 4 No operational N Y TBA Quote to be sent for approval. 30 in total, 4 not working. Recommendation for LED upgrade as current lights are discontinued.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Watch Cabinet Shop Floor Drawers are sticking N N Repairs to be done on service job 37348
3 Drawer Vitrines x 2 Shop Floor Drawers are sticking N N Repairs to be done on service job 37348
Feature Vitrine Shop Floor Drawers are sticking N N Repairs to be done on service job 37348
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE Powder 4.5kg 10/18 6/18 Green Zone BOH Y
Next Test Due in 3 months22/04/2019
Site Status SelectorStore now fully compliant
Technician's NameMorgan Jackson
Store Manager's NameHana Tamplin