Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateNSW
Date of Visit28/01/2019
Technician's NameShane Hamilton
Built Job Number36431
Swarovski Site in NSWliverpool
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (12 Month)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 2 Y 27 36 P
3 Y 38 29 P
4 Y 19 9 P
6 Y 18 8 P
7 Y 19 9 P
8 Y 19 10 P
9 Y 18 8 P
10 Y 38 47 P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 1 R Y Y Y P
2 R Y Y Y P
3 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 4 BOH Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Comments

Various glass cabinets on shop floor require quite a bit of force to close (seems as though hinges have dropped causing it to not close easily).

Locks work on all fixtures?No
Comments

Various locks do not work and require fiddling around in order to open/close cabinets.

Is there chips, dents or defects to joinery?Yes
Is there damage to skirtings?Yes
Comments

Skirtings are becoming loose and falling down overtime, only held in by Blue-Tac.

General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Comments

Good

Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?No
Comments

No shutter, but front door cover up plate is loose and moves as you open and close door, needs to be fixed.

General cleanliness of Façade? - provide detailsGood
Comments

Good

Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
Any issues found onsite please take photos and upload hereAny issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Cabinet track light x 9 (1 out) Shop floor 2 LED patch N N TBA If repairs are required, please send work request to service@builtelectrical.com.au
Cabinet track light x 9 (4 out) Shop floor 1 LED patch N N TBA If repairs are required, please send work request to service@builtelectrical.com.au
Cabinet track light x 5 (1 out) Shop floor 1 LED patch N N TBA If repairs are required, please send work request to service@builtelectrical.com.au
Square Downlight Shop floor 1 35W Transformer and lamp Y N N
Picture Sign Shop floor right side 4 36W 865 lamps, loose tombstone Y N N
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
C02 Fire Extinguisher BOH Testing required N N John approved works via email 1/2/19
Glass Cabinet Various Various glass cabinets on shop floor require quite a bit of force to close (seems as though hinges have dropped causing it to not close easily). N N John approved works via email 1/2/19
Cabinet Locks Various Various locks do not work and require fiddling around in order to open/close cabinets. N N John approved works via email 1/2/19
Cabinets Various Skirtings are becoming loose and falling down overtime, only held in by Blue-Tac. N N John approved works via email 1/2/19
Front Door Cover Front Door No shutter, but front door cover up plate is loose and moves as you open and close door, needs to be fixed. N N John approved works via email 1/2/19
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
C02 3.5kg 06/2018 04/2018 N BOH N
Next Test Due in 3 months28/04/2019
Site Status SelectorCompleted but with repairs required
Technician's NameKeith Haly
Store Manager's NameLesley Catlow