Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
No
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
Db1
1
R
Y
Y
Y
P
2
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
Db1
1
Y
N
Y
F
Failed 90 Min Test
Y
N
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
No
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
No
Comments
Scratches, marks
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
No
Comments
Various locks missing or not working (behind counter storage x 4, bracelet display x 1)
Front door seems loose when locked, staff concerned about safety
Is there chips, dents or defects to joinery?
Yes
Is there damage to skirtings?
Yes
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Comments
Staff concerned storage in BOH is OHS issue
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Window Box
Front window
2
Damaged and non compliant cabling
N
Y
TBA
Quote to be sent for approval for repairs.
Recessed Exit Light
01
1
Failed 90 Min Test
Y
N
N
36W 840 Lamps
Various
2
Faulty
Y
N
N
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?
Yes
General List of Repairs and additional works required
Defect Item
Location of Item
Details of Problem
Repaired on Site
Quote to be Sent
Comments
ABE Fire Extinguisher
BOH
Requires testing
N
N
John approved repairs via email on 18/2/19
Various Cabinets
Shop floor
Various locks missing or not working (behind counter storage x 4, bracelet display x 1)
N
N
John approved repairs via email on 18/2/19
B3 Vitrine 100 Free Cabinet
Shop floor
Lock not working
N
N
Being repaired on job 31780
Lock
Front Door
Front door seems loose when locked, staff concerned about safety
N
N
John approved repairs via email on 18/2/19
Storage
BOH Area
Staff concerned storage in BOH is OHS issue
N
N
John approved repairs via email on 18/2/19
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
ABE Powder
4.5kg
07/2018
05/2018
Green
BOH
N
Next Test Due in 3 months
13/05/2019
Site Status Selector
Completed but with repairs required
Technician's Name
Eddie Zaida
Store Manager's Name
Rebecca Meredith