Is there an Emergency Light Test Facility & is it labelled properly?
Yes
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
No
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
Yes
Comments
Slight marks on the ceiling near hanging light fitting.
Slight damage to plaster near front man hole.
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
Yes
Is there chips, dents or defects to joinery?
No
Is there damage to skirtings?
No
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Light Box
Shopfloor
1
Wiring is taped to the floor from flex running from ground
N
N
TBA
Raised under Service Job# 40356
3-Spot Crystal lights
Column - Bottom
5
Failed to illuminate
N
N
TBA
Lights need to be ordered. If repairs are required, please send work request to service@builtelectrical.com.au
3-Spot Crystal lights
Column - Top
13
Failed to illuminate
N
N
TBA
Faulty spots near the glass wall will be impossible to replace due to very limited space and EWP GR20 required to access. If repairs are required, please send work request to service@builtelectrical.com.au
36W Fluorescent lamp
BOH
1
Failed to illuminate
N
Y
TBA
Attempted to replace but found out the whole fitting requires replacement. Suggest upgrading to LED. If repairs are required, please send work request to service@builtelectrical.com.au
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
Powder ABE
2.5kg
MARCH 19
09/18
Green
BOH
Y
Next Test Due in 3 months
01/08/2019
Site Status Selector
Store now fully compliant
Technician's Name
Nathan McBain
Store Manager's Name
Irene Huynh