Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
Yes
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
Db1
Em1
R
Y
Y
Y
P
Em2
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
Db1
Ex1
Y
Y
Y
P
Ex2
Y
Y
Y
P
Ex3
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
No
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
No
Comments
Marks on walls, dirt, scratches.
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
No
Comments
1 x Jewellery display locking pin misses locking hole. Need to push glass doors in a little to lock cabinet.
1 x Jewellery vitrine located straight under light box missing lock.
1 x watch vitrine faulty, jammed lock, previously removed on service call. Asked by staff to remove lock from 'Always On' vitrine and fitted to watch vitrine. Watch vitrine bars are loose and get caught on joinery. Lock hard to turn.
(Issues being addressed on service job 34737)
Is there chips, dents or defects to joinery?
Yes
Comments
Chips and scratches on joinery
Is there damage to skirtings?
Yes
Comments
Marks on most skirtings
General cleanliness of fixtures, ceilings, P.O.S - provide details
Poor
Comments
Dirty marks on ceiling panels
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
No
Comments
N/A
General cleanliness of Façade? - provide details
Poor
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
No
Comments
Both front door handles very loose.
Front doors very hard to open.
Front doors very hard to lock, door locks don't line up with latching points.
Was able to remove both front door handles and tighten both internal bolts.
Front door handles are now OK.
Any issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Window boxes at entry, the cables are really swuashed.
Entry
2
Required a second person to be able to lift box and see condition of cabling. Box too low to be able to lift flap.
Y
N
N
As per John's email 26/7/19, techs approved to return to check cabling ASAP. Completed 1/8/19.
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
Carbon
2kg
02/2019
08/2015
Green
BOH
Y
Next Test Due in 3 months
23/10/2019
Site Status Selector
Store now fully compliant
Technician's Name
Eddie Zaida
Store Manager's Name
Rosalin Zhou
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.