Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateNSW
Date of Visit24/07/2019
Technician's NameKeith Haly
Built Job Number41819
Swarovski Site in NSWpenrith
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-T8B 1 Y P
4 Y P
5 Y P
6 Y P
7 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-T8B 1 R Y Y Y P
2 R-BOH Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-T8B 1 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?No
Comments

1 x draw is unable to close fully

Locks work on all fixtures?Yes
Comments

1 set of locks - Store Manager does not have keys to open it, number on lock is 07001
(Key has been sent to Store Manager)

Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Comments

N/A

General cleanliness of Façade? - provide detailsGood
Comments

Water damage has gotten worse since last audit. There is more mould showing behind counter on gyprock ceiling.

Lighting operational, (eg logo)?Yes
Comments

Canvas display light wiring is getting old and fragile with cracks in the sheath due to time and overheating. Down the track we might have to replace with LED strip lighting or linkable LED fluoro's. Otherwise we will have to replace wiring and ballasts.

Windows clean?Yes
Door handles clean and tight?No
Comments

Shop entry door handles have come loose on both glass doors.

Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
5 Spot LED Track Light Shop Floor 1 1 x lamp out N N TBA If repairs are required, please send request to service@sturdie.com.au.
9 Spot LED Track Light Shop Floor 1 1 x lamp out N N TBA If repairs are required, please send request to service@sturdie.com.au.
7 Spot LED Track Light Shop Floor 1 1 x lamp out N N TBA If repairs are required, please send request to service@sturdie.com.au.
Swarovski canvas light display Shop Floor 8 Lamps out Y N N
Swarovski canvas light display Shop Floor Various Wiring getting old and fragile, may need to be replaced with LED strip lights (see above notes) N Y TBA Quote to be provided.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Cabinet Drawer Shop floor 1 x draw unable to close fully N N To be repaired during next audit as per John.
Lock Set Lock number 07001 Manager does not have key to open Y N Key has been sent to Store Manager.
Ceiling Behind Counter Water damage on gyprock N N John, please arrange repairs.
Shop Entry Doors Front of store Door handles are loose N N To be repaired during next audit as per John.
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
Dry Powder 4.5kg 07/2019 10/2011 Y BOH Y
Next Test Due in 3 months24/10/2019
Site Status SelectorStore now fully compliant
Technician's NameKeith Haly
Store Manager's NameLesley Catlow