Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateNSW
Date of Visit29/07/2019
Technician's NameCon Karakiozis
Built Job Number41822
Swarovski Site in NSWbondi_junction
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Tbl3 south 2 Y P
Tbl3 south 3 Y P
Tbl3 south 4 Y P
Tbl3 5 Y P
Tbl3 6 Y P
Tbl3 south 7 Y P
Tbl3 south 8 Y P
Tbl3 south 9 Y P
Tbl3 south 10 Y P
Tbl3 south 11 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 Em1 R Y Y Y P N N N
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?No
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?No
Comments

Scratches and paint fading

Fixture draws able to open and close freely?No
Comments

Watch display units 1 and 2 - draws get stuck and do not open at all times

Locks work on all fixtures?No
Comments

Display unit in middle of store - lock gets stuck and sometimes does not open

Is there chips, dents or defects to joinery?Yes
Comments

All around store

Is there damage to skirtings?Yes
Comments

Skirting in some areas looks bubbled

General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?No
Comments

N/A

General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?No
Comments

3 x downlight lamps/fittings not working (as above)

Windows clean?Yes
Door handles clean and tight?Yes
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency Test Switch Switchboard 1 Does not exist N Y TBA Quote to be sent for approval.
Window Display Box Front of Store 1 TPS cable on floor and is a hazard every time staff move display unit. N Y TBA Floor power point will need to be installed and mechanical protection over cable. Quote to be sent for approval.
Downlights Front display window 3 Faulty lamps and/or fittings N N TBA Unable to reach, require 12 ft ladder and 2 x techs. If repairs are required, please send request to service@sturdie.com.au.
9 Spot Track Light Joinery unit near front left side 2 Top shelf has one light out and one light out on the second shelf N N TBA If repairs are required, please send request to service@sturdie.com.au.
9 Spot Track Light Joinery 2 unit near front left side 3 Top shelf has two lights out and one light out on the second shelf N N TBA If repairs are required, please send request to service@sturdie.com.au.
9 Spot Track Light Joinery unit 3 near front entry left side 3 Top shelf has one light out and one light out on the third shelf N N TBA If repairs are required, please send request to service@sturdie.com.au.
9 Spot Track Light BOH wall joinery unit 3 Top shelf has one light out and two lights out on the second shelf N N TBA If repairs are required, please send request to service@sturdie.com.au.
9 Spot Track Light Right side of entry joinery unit 1 2 Top shelf has one light out and one light out on the second shelf N N TBA If repairs are required, please send request to service@sturdie.com.au.
6 Spot Track Light Right side of entry joinery unit 3 2 Top shelf has one light out and one light out on the last shelf N N TBA If repairs are required, please send request to service@sturdie.com.au.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Fire Extinguisher BOH Testing required - overdue N N To be addressed once new schedule is confirmed in Service Channel.
Watch Display Unit Shop Floor Unit 1 & 2, draws get stuck and do not always open N N To be repaired during re-furb by other contractors.
Display Unit Middle of store Lock gets stuck and sometimes does not open. N N John approved repairs via email 29/7/19.
Skirtings Throughout store Appears to be bubbled in areas N N To be repaired during re-furb by other contractors.
Joinery & Walls Throughout store Chips, scratches and fading N N To be repaired during re-furb by other contractors.
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
Carbon Dioxide 3kg 12/2018 01/2018 N/A BOH N
Next Test Due in 3 months25/10/2019
Site Status SelectorStore now fully compliant
Technician's NameCon Karakiozis
Store Manager's NameStephanie M