Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateNSW
Date of Visit13/08/2019
Technician's NameKeith Haly
Built Job Number41831
Swarovski Site in NSWmiranda
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 2 Y P
MDB 3 Y P
MDB 4 Y P
MDB 5 Y P
MDB 6 Y P
MDB 7 Y P
MDB 8 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?No
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MDB Showroom R Y Y Y P . . .
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
There are no exit lights. Not required as it is a new shop.
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Comments

One island bay - 1 cabinet doesn't lock and the other lock requires fiddling to lock.

Is there chips, dents or defects to joinery?No
Is there damage to skirtings?Yes
Comments

Throughout the shops the edges of the skirting are starting to peel off, but they are not too bad,

General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?Yes
Comments

Large canvas display (facing outside to the wall) - LED strip is not bright enough. Recommend replacing with more LED strips or LED linkable fluoro lights.

Windows clean?Yes
Door handles clean and tight?Yes
Any issues found onsite please take photos and upload hereAny issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Switch Mechanism BOH light switch 1 Faulty Y N N
21W 840 Lamp Shop floor 4 Faulty Y N N
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Large Canvas Display Shop Floor LED strip is not bright enough. Recommend replacing with more LED strips or LED linkable fluoro lights. N Y Quote to be sent for approval.
Island Cabinets Shop Floor 1 cabinet doesn't lock and the other lock requires fiddling to lock. N N John, please advise if repairs are required.
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABC Dry Powder 3.0kg 11/2018 03/2014 Y BOH Due to be tested October 2019.
Next Test Due in 3 months13/11/2019
Site Status SelectorStore now fully compliant
Technician's NameKeith Haly
Store Manager's NameAngela Bezjak Angela Bezjak