Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
Yes
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
1
1
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
1
2
Y
Y
Y
Y
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
Yes
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
Yes
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
Yes
Is there chips, dents or defects to joinery?
Yes
Comments
Back door and window display boxes - touched up/repaired.
Is there damage to skirtings?
Yes
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
Yes
Comments
Front entry Swarovski sign chrome banner display missing end cap. See photo attached.
Windows clean?
Yes
Door handles clean and tight?
Yes
Any issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
7 Spot LED Light
Right window display
1
4 spots out
N
N
TBA
Please advise if repairs are required.
7 Spot LED Light
Right window display
1
1 spot out (second shelf)
N
N
TBA
Please advise if repairs are required.
7 Spot LED Light
Right side of store middle display unit
2
2 spots out (1 on top shelf and 1 on second shelf)
N
N
TBA
Please advise if repairs are required.
7 Spot LED Light
Right side of store last display unit
1
3 spots out (top shelf)
N
N
TBA
Please advise if repairs are required.
Display Unit
Right side of entry
2
Swarovski logo not illuminated
N
Y
TBA
Two techs required to remove shelves in order to access light power supply. Quote to be sent for approval. Pre Trade works recommended.
Wall Display Units
Front entry wall display units
2
Store has requested that one wall display be on 24 hr power and the other to be controlled by light switch.
N
Y
TBA
Two techs required to pull apart wall display wiring and rewire. Store will need to remove stock from top and second shelves. Job will need to be completed before trade or after trade. Quote to be sent for approval.
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
Carbon Dioxide
3.5kg
11/2019
09/2018
N/A
BOH near sink
Y
Next Test Due in 3 months
21/06/2020
Site Status Selector
Store now fully compliant
Technician's Name
Con Karakiozis
Store Manager's Name
Lisawati Gan