| Which Company are you working for? | Sturdie Trade Services |
|---|
| Which Trade are you working for? | Electrical |
|---|
| State | NSW |
|---|
| Date of Visit | 29/01/2020 |
|---|
| Technician's Name | Eddie Zaida |
|---|
| Built Job Number | 46683 |
|---|
| Swarovski Site in NSW | liverpool |
|---|
| Test Period | 6 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| RCD Details (6 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DB |
2 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
- Report any failures and provide costing to rectify (where applicable)
|
|---|
| Is there an Emergency Light Test Facility & is it labelled properly? | Yes |
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB BOH |
1 |
R |
Y |
Y |
Y |
P |
|
|
|
|
2 |
R |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB BOH |
1 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au | Yes |
|---|
| If Yes, please upload all copies of legends here... (Limit of 6 megabytes total) | Swarovski-Liverpool-Switchboard-Legend.pdf |
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| Window Display Boxes - Is the Cabling in good conditions? | Yes |
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| Paint & surfaces are clean? | No |
|---|
| Comments | Marks and scrapes - paint pen will not fix
|
|---|
| Fixture draws able to open and close freely? | Yes |
|---|
| Locks work on all fixtures? | No |
|---|
| Comments | Watch vitrine does not lock - arms broken, no part available
|
|---|
| Is there chips, dents or defects to joinery? | Yes |
|---|
| Comments | Chips throughout store
|
|---|
| Is there damage to skirtings? | Yes |
|---|
| Comments | Dirty and unstuck in some spots
|
|---|
| General cleanliness of fixtures, ceilings, P.O.S - provide details | Good |
|---|
| Comments | Floor and man holes have dirty marks
|
|---|
| Any issues found onsite please take photos and upload here | |
|---|
| Roller shutters in working order and clean? | No |
|---|
| Comments | N/A
|
|---|
| General cleanliness of Façade? - provide details | Average |
|---|
| Comments | Metal signage dusty
|
|---|
| Lighting operational, (eg logo)? | Yes |
|---|
| Windows clean? | No |
|---|
| Comments | Hand prints and marks
|
|---|
| Door handles clean and tight? | Yes |
|---|
| ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Downlight |
Retail Floor |
1 |
Not illuminating |
N |
N |
Y |
Light to be ordered, to be replaced on separate GL job |
| Swan |
Behind counter |
1 |
Not illuminating |
N |
N |
N |
Current service job 46320 |
| 9 Way Up Light |
Columns |
1 |
Missing spots |
N |
Y |
TBA |
Whole timber panels need to be removed |
| 9 Spot Light |
Cool Romance Display |
1 |
1 spot out - still sufficient light |
N |
N |
N |
|
| Test & Tag |
Various |
13 |
Testing and tagging required |
Y |
N |
N |
Completed |
| Air Conditioner |
Ceiling |
1 |
Needed to be reset from electrical fault |
Y |
N |
N |
|
|
|---|
| General Works Checklist | - Inspect all furniture and fittings for visible damage
- Inspect all walls, ceilings, skirtings and floors for visible damage
- Inspect storefront, façade and store LED logo for correct operations and visible damage
- Inspect roller shutter and doors for correct operations and visible damage
- Check fire extinguishers, update compliance tags/labels
|
|---|
| Are there any repairs and additional works required? | Yes |
|---|
| General List of Repairs and additional works required | | Defect Item |
Location of Item |
Details of Problem |
Repaired on Site |
Quote to be Sent |
Comments |
| Front Entry Door |
Front of store |
Swings past stopper |
N |
N |
Current service job 45182 |
| Swarovski Metal Sign |
Front of store |
End caps missing |
N |
N |
Parts to be sourced and ordered |
|
|---|
| Fire Extinguisher Details | | Type (ABE Powder) |
Size (4.5kg) |
Last Test Date |
Manufacture Date |
Pressure Indicator (Green Zone) |
Location In Store |
Compliant (Y/N) |
| CO2 |
3.5kg |
11/2019 |
04/2018 |
Green |
BOH |
Y |
|
|---|
| Next Test Due in 3 months | 29/02/2020 |
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Technician's Name | Eddie Zaida |
|---|
| Store Manager's Name | Store Manager |
|---|
| |
|---|
| |