Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
Yes
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB
Showroom
R
Y
Y
Y
P
DB
BOH
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB
1
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
Yes
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
Yes
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
No
Comments
2 x glass display locks jam up and sometimes do not open or close. Locksmith has attended many times but issue is recurring. This has now become a security issue. Locks need to be replaced.
1 x display cabinet in center of store - does not lock the cupboard and the sliding display above which is a security issue.
(Both to be repaired on job 50801)
Is there chips, dents or defects to joinery?
Yes
Comments
Joinery unit at back of store has multiple chips and will need replacing. Photo attached.
Is there damage to skirtings?
No
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
Yes
Comments
N/A - No shutter
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
Yes
Any issues found onsite please take photos and upload here
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
LED Spot - Mirror Column
Front display window
7
7 x LED spots out
N
N
Y
To be completed on job 50816 as approved by John Cowles.
LED - Display Cabinet
Near BOH Door
2
2 x LED lamps out
N
N
Y
To be completed on job 50816 as approved by John Cowles.
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?
Yes
General List of Repairs and additional works required
Defect Item
Location of Item
Details of Problem
Repaired on Site
Quote to be Sent
Comments
Light Panel Diffusers
BOH
2 x Broken light diffusers
N
N
To be completed on job 50816 as approved by John Cowles.
Light Fitting
BOH
One light fitting has the wrong colour lamps and will need to be replaced
N
N
To be completed on job 50816 as approved by John Cowles.
Sound System
BOH
Not working. Has been sent back to Swarovski IT for repairs, still not working.
N
N
To be completed on job 50816 as approved by John Cowles.
Fire Extinguisher
BOH
Not compliant - requires testing
N
N
To be tested late July/early August as per approval from John Cowles.
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
ABE Powder Type
4.5kg
12/2019
05/2018
Y
BOH
N
Next Test Due in 3 months
17/12/2020
Site Status Selector
Completed but with repairs required
Technician's Name
Con Karakiozis
Store Manager's Name
Tania simon Simon