Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateVIC
Date of Visit19/01/2021
Technician's NameNathan McBain
Built Job Number53961
Swarovski Site in VICbourke_street_mall
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 DOWNSTAIRS 07 Y P
08 Y P
09 Y P
10 Y P
11 Y P
12 Y P
13 Y P
DB2 UPSTAIRS 02 Y P
03 Y P
04 Y P
05 Y P
06 Y P
07 Y P
08 Y P
09 Y P
10 Y P
11 Y P
12 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
EM01 R Y Y Y P
EM02 R Y Y Y P
EM03 R Y N Y F FAILED BATTERY TEST Y N
EM04 R Y Y Y P
EM05 R Y Y Y P
EM06 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
EX01 Y Y Y P
EX02 Y Y Y P
EX03 Y Y Y P
EX04 Y Y Y P
EX05 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
  • Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Locks work on all fixtures?No
Comments

1 × VITTRINE CABINET LOCK/BARREL REQUIRES REPLACEMENT, LOCK REMOVED BY TEAM MEMBER DUE TO HAVING KEY STUCK IN BARREL, ALL OF LOCKING MECH HAS BEEN REMOVED BY TEAM MEMBER TO GAIN ACCESS.

MAJORITY OF VITTRINE CABINETS HAVE LOCKING ISSUES AS PER PREVIOUS AUDITS.

Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?No
Comments

PUSH BUTTON EXIT NOT WORKING ON FRONT ENTRANCE. FOUND FAULTY CONNECTION BEHIND PUSH BUTTON.

General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG STORE 30-40 TEST AND TAG EXPIRED 18/09/2020 N TBA TBA SENT TO JOHN FOR APPROVAL
DOWNLIGHT FEMALE TOILET 1 FAILED TO ILLUMIMATE Y N N FOUND LOOSE CONNECTION. RECONNECTED ON SITE.
PUSH BUTTON EXIT FRONT ENTRANCE 1 DOOR NOT OPENING WHEN PUSH BUTTON PRESSED Y N N FOUND FAULTY CONNECTION BEHIND BUTTON. RECONNECTED ON SITE.
5 SPOT WALL SMALL GLASS CABINET 1 LIGHT OF 5 SPOT FAILED TO ILLUMINATE Y N N REPAIRED ON SITE UNDER WORK ORDER 142550156
EM03 UPSTAIRS STAFF NEAR KITCHEN 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - PROPOSAL SUBMITTED FOR PAYMENT (prp11921043500403)
FRONT AUTOMATIC DOOR FRONT ENTRANCE 1 MANAGER INFORMED THAT OCCASIONALLY FRONT DOOR WILL NOT CLOSE ALL THE WAY AND REQUIRES A PUSH TO CLOSE COMPLETELY N TBA TBA SENT TO JOHN FOR APPROVAL
SECURITY SYSTEM STORE 1 MANAGER INFORMED THAT SECURITY SYSTEM HAS NOT WORKED FOR A VERY LONG TIME. ATTENDED BY SECURITY TECH LAST YEAR DUE TO WATER DAMAGED, TECH FIXED BUT INFORMED MANAGER FAULT WOULD REOCCURE, HAS NOT WORKED SINCE. TECH ALSO INFORMED MANAGER A REWIRE WOULD BE REQUIRED. N TBA TBA FYI
VITTRINE CABINET WALL 1 BARREL DAMAGE/KEY BROKEN INSIDE, HAS BEEN REMOVED BY FLOOR STAFF N TBA TBA SENT TO JOHN FOR APPROVAL
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, note compliance date
  • Make sure all cabinet door hinges are firmly secured
  • Check there is No Tripping Hazards in the sales or backroom areas
  • Inspect plumbing is working as intended. If no, note in general repairs and repair where possible
Are there any repairs and additional works required?No
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE POWDER 4.5KG FEB 2021 05/11 GREEN BOH Y
WATER TYPE 9.1KG MAR 2021 01/11 GREEN STAFF AREA TOP OF STAIRS Y
ABE POWDER 4.5KG MAR 2021 GREEN UPSTAIRS NEAR LUNCHROOM Y
ABE POWDER 2.5KG MAR 2021 GREEN UPSTAIRES COMMS ROOM Y
Next Test Due in 3 months19/07/2021
Site Status SelectorStore now fully compliant