Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateWA
Date of Visit15/01/2021
Technician's NameJames Patterson
Built Job Number54365
Swarovski in WAbooragoon
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Tenancy 69 DB 1 Y P N
2 Y P N
3 Y P N
4 Y P N
5 Y P N
6 Y P N
7 Y P N
8 Y P N
9 Y P N
10 Y P N
11 Y P N
12 Y P N
13 Y P N
14 Y P N
15 Y P N
16 Y P N
17 Y P N
18 Y P N
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Tenancy 69 DB 1 R Y Y Y P
2 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Tenancy 69 DB 3 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
  • Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)Swarovski-Booragoon-Switchboard-Legend.pdf
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?Yes
Paint & surfaces are clean?No
Comments

Front of store has had water damage on ceiling. When it rains, it leaks.
Centre Management are aware. To be repaired by Shopping Centre

Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Roller shutters in working order and clean?Yes
Comments

Not Applicable

General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?No
Comments

1 x 2by28w troffer was not illuminated at BOH. Has now been repaired on site.

Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
2by28w troffer BOH 1 Not illuminated Y N N
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Front ceiling leak Front of store Water leak N N Centre Management to repair
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE Powder 2.5kg July 2020 October 2018 Green Zone (11 Bar) BOH N - To be serviced between 15/01/21 - 29/01/21
Next Test Due in 3 months15/07/2021
Site Status SelectorStore now fully compliant
Technician's NameJames Patterson
Store Manager's NameAlyshia Harrison