Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateNSW
Date of Visit27/01/2021
Technician's NameEddie Zaida
Built Job Number53932
Swarovski Site in NSWliverpool
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
BOH Y P
DB Showroom Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB BOH Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
  • Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auNo
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?No
Comments

Marks and scrapes

Fixture draws able to open and close freely?Yes
Locks work on all fixtures?No
Comments

Lock on styling vitrine below light box very hard to lock and unlock, not approved for repair at this stage.

Is there chips, dents or defects to joinery?Yes
Comments

Large amount of chips in BOH door. Paint pen runs as it on the vertical.

Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Roller shutters in working order and clean?No
Comments

N/A

General cleanliness of Façade? - provide detailsPoor
Comments

Very dusty

Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
36W Lamps Front light boxes 5 Not illuminated Y N N Originally has 36w 865, replaced with 36w 840 as no 865s in car. Just to get signage lit. Can change to 865's next PM
36W Lamps Front signage 2 Not illuminated N N Y Changed lamps but ballast is required. Will need to order electronic ballast
Downlight Retail floor 1 Not illuminating N N N EzyAs LED to replace
Swan Logo Behind counter 1 Not illuminated N N N Need a shop fitter to dismantle joinery to get to LEDs and drivers. Have attempted previously.
Column lights 3ways Columns 9 At least 1 out in each 3 way N N N Not approved for repair.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, note compliance date
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
End Caps Front signage Missing inserts Y N N
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE 2.0kg 6/2020 1/2020 Green BOH Y
Next Test Due in 3 months28/07/2021
Site Status SelectorStore now fully compliant
Technician's NameEddie Zaida
Store Manager's NameSna .