Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateVIC
Date of Visit29/01/2021
Technician's NameNathan McBain
Built Job Number53974
Swarovski Site in VICdoncaster
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB 02 Y P
03 Y P
04 Y P
05 Y P
06 Y P
07 Y P
08 Y P
09 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?No
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB EM02 R Y Y Y P
EM03 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB EX01 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
  • Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?Yes
Fixture draws able to open and close freely?Yes
Locks work on all fixtures?No
Comments

6 × Vittrine cabinets not locking

Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?Yes
Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
EMERGENCY TEST FACILITY MSB 1 NO TEST FACILITY INSTALLED N TBC TBC EMAILED JOHN
TEST AND TAG STORE 20 NEXT TEST AND TAG DUE 12_03_21 N N N EMAILED JOHN
RECESSED SQUARE SHOP LIGHTS SALES FLOOR 5 FAILED TO ILLUMINATE N TBC TBC 4.0M TO CEILING, 10FT STEPS REQUIRED, BEFORE TRADE. EMAILED JOHN
WALL CRSTAL SPOTS NORTH WALL 8 × 4 SPOT AND 2 × 3 SPOT (ALL) FAILED TO ILLUMINATE N TBC TBC 4.0M TO CEILING. FOUND 24V CABLE COMING FROM TOP CRYSTAL SPOT SUPPLING BOTTOM CRYSTAL SPOTS, TESTED NO VOLTAGE, POSSIBLE FAULTY DRIVER, DRIVER POSSIBLY SITUATED IN CEILING SPACE, INVESTIGATE FURTHER WHEN 10FT LADDER ONSITE. EMAILED JOHN.
WALL CRSTAL SPOTS SOUTH WALL BOTTOM 1 × 3 SPOT. TOP 2 × 4 SPOT FAILED TO ILLUMINATE N TBC TBC EMAILED JOHN
CENTER COLUMN CRSTAL SPOTS SALES FLOOR BOTTOM 1 × 3 SPOT, TOP 8 × 3 SPOT FAILED TO ILLUMINATE N TBC TBC EMAILED JOHN
9 SPOT GLASS WALL CABINET NORTH WALL 1 × 9 SPOT 1 GLOBE OUT ON 1× 9 SPOTS FAILED TO ILLUMINATE N TBC TBC PLEASE ADVISE IF STURDIE IS TO REPAIR.
9 SPOT GLASS WALL CABINET NORTH WALL 1 × 9 SPOT 1 GLOBE OUT ON 1× 9 SPOTS FAILED TO ILLUMINATE N TBC TBC PLEASE ADVISE IF STURDIE IS TO REPAIR.
9 SPOT GLASS WALL CABJNET SOUTH WALL 1 × 9 SPOT 1 GLOBE OUT ON 1× 9 SPOTS FAILED TO ILLUMINATE N TBC TBC PLEASE ADVISE IF STURDIE IS TO REPAIR.
VITTRINE CABINETS SALES FLOOR 6 × CABINETS FAULTY LOCKS N TBC TBC ALL VITTRINE CABINETS HAVE HAD LOCKING PIN/HASP REMOVED FROM SIDES OF DRAWS, 2 PER DRAW, 3 DRAWS PER VITTRINE CABINET. LOCKS HAVE NOT WORKED ON VITTRINE CABINETS FOR 3 YEARS AS PER STORE MANAGER. WHEN KEY OPERATED LOCKING MECHANISM DOES NOT SEEM TO OPERATE. THIS IS BEING DISCUSSED WITH JOHN.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, note compliance date
Are there any repairs and additional works required?No
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE POWDER 2.5KG NOV 2020 01/2012 GREEN BOH Y
Next Test Due in 3 months29/07/2021
Site Status SelectorStore now fully compliant
Technician's NameNATHAN MCBAIN
Store Manager's NameJenny Noone