Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
No
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MSB
EM02
R
Y
Y
Y
P
EM03
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MSB
EX01
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
Yes
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
Yes
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
No
Comments
6 × Vittrine cabinets not locking
Is there chips, dents or defects to joinery?
No
Is there damage to skirtings?
No
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
EMERGENCY TEST FACILITY
MSB
1
NO TEST FACILITY INSTALLED
N
TBC
TBC
EMAILED JOHN
TEST AND TAG
STORE
20
NEXT TEST AND TAG DUE 12_03_21
N
N
N
EMAILED JOHN
RECESSED SQUARE SHOP LIGHTS
SALES FLOOR
5
FAILED TO ILLUMINATE
N
TBC
TBC
4.0M TO CEILING, 10FT STEPS REQUIRED, BEFORE TRADE. EMAILED JOHN
WALL CRSTAL SPOTS
NORTH WALL
8 × 4 SPOT AND 2 × 3 SPOT (ALL)
FAILED TO ILLUMINATE
N
TBC
TBC
4.0M TO CEILING. FOUND 24V CABLE COMING FROM TOP CRYSTAL SPOT SUPPLING BOTTOM CRYSTAL SPOTS, TESTED NO VOLTAGE, POSSIBLE FAULTY DRIVER, DRIVER POSSIBLY SITUATED IN CEILING SPACE, INVESTIGATE FURTHER WHEN 10FT LADDER ONSITE. EMAILED JOHN.
WALL CRSTAL SPOTS
SOUTH WALL
BOTTOM 1 × 3 SPOT. TOP 2 × 4 SPOT
FAILED TO ILLUMINATE
N
TBC
TBC
EMAILED JOHN
CENTER COLUMN CRSTAL SPOTS
SALES FLOOR
BOTTOM 1 × 3 SPOT, TOP 8 × 3 SPOT
FAILED TO ILLUMINATE
N
TBC
TBC
EMAILED JOHN
9 SPOT
GLASS WALL CABINET NORTH WALL
1 × 9 SPOT
1 GLOBE OUT ON 1× 9 SPOTS FAILED TO ILLUMINATE
N
TBC
TBC
PLEASE ADVISE IF STURDIE IS TO REPAIR.
9 SPOT
GLASS WALL CABINET NORTH WALL
1 × 9 SPOT
1 GLOBE OUT ON 1× 9 SPOTS FAILED TO ILLUMINATE
N
TBC
TBC
PLEASE ADVISE IF STURDIE IS TO REPAIR.
9 SPOT
GLASS WALL CABJNET SOUTH WALL
1 × 9 SPOT
1 GLOBE OUT ON 1× 9 SPOTS FAILED TO ILLUMINATE
N
TBC
TBC
PLEASE ADVISE IF STURDIE IS TO REPAIR.
VITTRINE CABINETS
SALES FLOOR
6 × CABINETS
FAULTY LOCKS
N
TBC
TBC
ALL VITTRINE CABINETS HAVE HAD LOCKING PIN/HASP REMOVED FROM SIDES OF DRAWS, 2 PER DRAW, 3 DRAWS PER VITTRINE CABINET. LOCKS HAVE NOT WORKED ON VITTRINE CABINETS FOR 3 YEARS AS PER STORE MANAGER. WHEN KEY OPERATED LOCKING MECHANISM DOES NOT SEEM TO OPERATE. THIS IS BEING DISCUSSED WITH JOHN.
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, note compliance date
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
ABE POWDER
2.5KG
NOV 2020
01/2012
GREEN
BOH
Y
Next Test Due in 3 months
29/07/2021
Site Status Selector
Store now fully compliant
Technician's Name
NATHAN MCBAIN
Store Manager's Name
Jenny Noone