Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
No
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MAIN DB
EM01
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MAIN DB
EX02
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
No
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
Yes
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
Yes
Fixture draws able to open and close freely?
No
Comments
1× VITTRINE CABINET EAST WALL SLIDING DISPLAY GETS CAUGHT WHEN TRYING TO SLIDE OUT, ADJUSTED AS PER WORK ORDER #159317867
Locks work on all fixtures?
No
Comments
2 × WALL GLASS CABINETS WEST WALL, 1ST AND 3RD FROM FRONT, LOCKS INTERMITTENTLY GETTING CAUGHT, RECOMMENED REPLACING 2 × 18305 BARRELS NEXT AUDIT
Is there chips, dents or defects to joinery?
No
Is there damage to skirtings?
No
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
Yes
Windows clean?
Yes
Door handles clean and tight?
Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
TEST AND TAG
STORE
1
NEXT TEST DUE 31_07_21
N
N
N
OBSERVATION
NO EMERGENCY TEST FACILITY
MAIN DB
1
NO TEST FACILITY INSTALLED.
N
TBA
TBA
EMAILED JOHN FOR APPROVAL TO INSTALL
PINE LIGHTS
FRONT FLOOR CABINET LHS
2
FAILED TO ILLUMINATE
Y
N
N
REPLACED DRIVER AND 2 × PINE LIGHTS
PINE LIGHTS
FRONT FLOOR CABINET LHS
2
FAILED TO ILLUMINATE
N
TBC
TBC
2 × FAULTY PINE LIGHT, DRIVER IS WORKING HOWEVER DRIVER INSTALLED IS SAIF SLT20-500IF-1 AND DOES NOT HAVE AUSTRALIAN TICK OF APPROVAL. RECOMMEND REPLACING DRIVER AND 2 × PINE LIGHTS. EMAILED JOHN FOR APPROVAL TO REPLACE.
PINE LIGHTS
FRONT FLOOR CABINETS RHS
2
FAILED TO ILLUMINATE
Y
N
N
FOUND CONNECTION UNPLUGED, RECONNECTED AND NOW WORKING AS INTENDED.
WATCH CABINET BARREL
WATCH CABINET
1
BARREL DIFFRENT TO REST OF STORE
Y
N
N
REPLACED 18303 BARREL FOR 18305 BARREL.
SB LEGEND
SB
1
NO LEGEND ON SITE
N
N
Y
LEGEND TO BE CREATED AND INSTALLED AT NEXT AUDIT
BARREL
GLASS WALL CABINETS WEST WALL 1ST AND 3RD FROM FRONT
2
BARRELS INTERMITTENTLY GETTING CAUGHT, WEAR AND TEAR
N
TBC
TBC
EMAILED JOHN FOR APPROVAL TO REPLACE
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, note compliance date
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
ABE POWDER
2.5KG
JAN 2021
07/2018
GREEN
BOH
Y
Next Test Due in 3 months
01/08/2021
Site Status Selector
Store now fully compliant
Technician's Name
NATHAN MCBAIN
Store Manager's Name
Steph Micheals