Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?
Yes
Timers
Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MAIN DB
EM01
R
Y
Y
Y
P
MAIN DB
EM02
R
Y
Y
Y
P
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MAIN DB
EX01
Y
Y
Y
P
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?
Yes
Are there any Warranty items needing to be repaired?
No
Paint & surfaces are clean?
No
Comments
BUILD UP OF BUGS/DUST BEHIND FRONT SIGN, NOT ACCESSIBLE. PHOTO ATTACHED.
Fixture draws able to open and close freely?
Yes
Locks work on all fixtures?
Yes
Is there chips, dents or defects to joinery?
No
Is there damage to skirtings?
No
General cleanliness of fixtures, ceilings, P.O.S - provide details
Good
Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?
Yes
General cleanliness of Façade? - provide details
Good
Lighting operational, (eg logo)?
No
Comments
SWAN LOGO BEHIND COUNTER FAILED TO ILLUMINATE.
Windows clean?
Yes
Door handles clean and tight?
Yes
Comments
TIGHTENED AND LUBRICATED HINGE AS IT WAS SQUEAKY
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
TEST AND TAG
STORE
10-15
TEST AND TAG IN DATE NEXT TEST DUE 24_03_2022
N
N
N
OBSERVATION
SWAN LOGO LIGHT
BEHIND COUNTER
2
FAILED TO ILLUMINATE 50%
N
TBA
TBA
DRIVER REQUIRES REPLACING. HOWEVER MANAGER ADVISED SIGN MAY BE GETTING REPLACED. PLEASE ADVISE IF STURDIE ARE TO PROCEED WITH REPAIRS FOR SIGN
FIRE EXTINGUISHER
BOH
1
EXISTING LOCATION, EXTINGUISHER MOUNTED TOO HIGH, NO TYPE SIGN OR LOCATION SIGN INSTALLED
N
N
Y
RELOCATED FIRE EXTINGUISHER TO CORRECT HEIGHT, ORDER AND REPLACE TYPE SIGN AND LOCATION SIGN, ONCE COMPLETED FIRE EXTINGUISHER CAN BE CERTIFIED. WORKS TO BE CARRIED OUT ON TRACKING 191030071
DYSON VACUUM
BOH
1
NO BRACKET INSTALLED
Y
N
N
INSTALLED DYSON WALL BRACKET WHILE ONSITE
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, note compliance date
Are there any repairs and additional works required?
No
Fire Extinguisher Details
Type (ABE Powder)
Size (4.5kg)
Last Test Date
Manufacture Date
Pressure Indicator (Green Zone)
Location In Store
Compliant (Y/N)
ABE POWDER
2.5KG
AUG 21
OCT-2019
GREEN
BOH
N
Next Test Due in 3 months
27/05/2022
Site Status Selector
Completed but with repairs required
Technician's Name
NATHAN MCBAIN
Store Manager's Name
Natae Aberle