Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateVIC
Date of Visit12/11/2021
Technician's NameNathan McBain
Built Job Number57751
Swarovski Site in VICnorthland
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 4-5 Y P
DB1 6-7 Y P
DB1 8 Y P
DB1 9 Y P
DB1 13 Y P
DB1 14 Y P
DB1 17 Y P
DB1 18 Y P
DB1 19 Y P
DB1 23-24 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 EM01 R Y Y Y P
DB1 EM02 R Y Y Y P
DB1 EM03 R Y Y Y P
DB1 EM04 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 EX01 Y Y Y P
DB1 EX02 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
  • Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?No
Comments

CRACKS IN CEILING PLASTER AS REPORTED

Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?No
Comments

FRONT SIGN SOUTH SIDE DIM AS REPORTED FACING PROUDS

Windows clean?Yes
Door handles clean and tight?No
Comments

EAST SIDE ENTRY HANDLE LOOSE, TIGHTEN WHILE ONSITE

ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG STORE 15+ TEST AND TAG INDATE, NEXT TEST DUE 26_01_22 N N N OBSERVATION
PINE LIGHTS CENTER OF SHOP SMALL CABINET EAST 2 FAILED TO ILLUMINATE N TBA TBA PINE LIGHTS AND DRIVERS REQUIRE REPLACING. PLEASE ADVISE IF STURDIE ARE TO PROVIDE A QUOTE.
PINE LIGHTS PHONE COVERS SOUTH 2 FAILED TO ILLUMINATE N TBA TBA PINE LIGHTS AND DRIVERS REQUIRE REPLACING. PLEASE ADVISE IF STURDIE ARE TO PROVIDE A QUOTE.
PINE LIGHTS CABINET NEXT TO PHONE COVERS SOUTH 2 FAILED TO ILLUMINATE N TBA TBA PINE LIGHTS AND DRIVERS REQUIRE REPLACING. PLEASE ADVISE IF STURDIE ARE TO PROVIDE A QUOTE.
PINE LIGHTS CENTER OF SHOP LARGE CABINET 4 FAILED TO ILLUMINATE/FLICKERING N TBA TBA 4 × PINE LIGHTS AND 2 × DRIVERS REQUIRE REPLACING AS THE LIGHTS ARE FLICKERING. PLEASE ADVISE IF STURDIE ARE TO PROVIDE A QUOTE.
SWAROVSKI SIGN FRONT OF STORE SOUTH 1 THE SWAN, V AND I IS ILLUMINATED HOWEVER THE REST OF THE SIGN IS VERY DIM N TBA TBA SIGN WILL REQUIRE REPLACING. PLEASE ADVISE IF STURDIE ARE TO PROVIDE A QUOTE.
CRACKS IN CEILING AROUND SPRINKLER HEAD AND AROUND LIGHTS NEAR AIR CONDITIONING VENTS, NEAR POS 2 CRACKS IN PLASTER N TBA TBA OBSERVATION
PINE LIGHTS NEAR ENTRY EAST SIDE 2 FAILED TO ILLUMINATE N TBA TBA PINE LIGHTS AND DRIVER REQUIRES REPLACING. PLEASE ADVISE IF STURDIE ARE TO PROVIDE A QUOTE.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, note compliance date
Are there any repairs and additional works required?No
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE POWDER 2.5KG NOV 21 10/2019 GREEN BOH Y
Next Test Due in 3 months12/05/2022
Site Status SelectorStore now fully compliant
Technician's NameNATHAN MCBAIN
Store Manager's NameNick H