Which Company are you working for?Sturdie Trade Services
Which Trade are you working for?Electrical
StateVIC
Date of Visit29/04/2022
Technician's NameNathan McBain
Built Job Number62410
Swarovski Site in VICnorthland
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 4-5 Y P
6-7 Y P
8 Y P
9 Y P
13 Y P
14 Y P
17 Y P
18 Y P
19 Y P
23-24 Y P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Is there an Emergency Light Test Facility & is it labelled properly?Yes
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 EM01 R Y Y Y P
EM02 R Y Y Y P
Em03 R Y Y Y P
Em04 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 EX01 Y Y Y P
EX02 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
  • Inspection of mobile & stationary electrical appliances
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Window Display Boxes - Is the Cabling in good conditions?Yes
Are there any Warranty items needing to be repaired?No
Paint & surfaces are clean?No
Comments

CRACKS IN CEILING BETWEEN LIGHT FITTING AND CORNER OF AC VENT (CLOSEST TO OSCAR WYLEE STORE)

CRACKS IN CEILING ABOVE COUNTER.

Fixture draws able to open and close freely?Yes
Locks work on all fixtures?Yes
Is there chips, dents or defects to joinery?No
Is there damage to skirtings?No
General cleanliness of fixtures, ceilings, P.O.S - provide detailsGood
Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
  • Any issues found onsite please take photos and upload here
Roller shutters in working order and clean?Yes
General cleanliness of Façade? - provide detailsGood
Lighting operational, (eg logo)?No
Comments

1 × FRONT SIGN SOUTH SIDE DIM AS REPORTED FACING PROUDS

Windows clean?Yes
Door handles clean and tight?Yes
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LARGE VISUAL SIGN FACING PROUDS 1 FAILED TO ILLUMINATE N N TBA FAULTY DRIVER HLG-240H-24, HOWEVER DUE TO AGE OF FITTING IN VISUAL DISPLAY RECOMMEND REPLACING DRIVER AND INSTALLING NEW LED STRIP, SAME AS OTHER VISUAL SIGN THAT WAS REPAIRED ONSITE.. 1500×2400.
PINE LIGHTS SHOP FLOOR 11 DUE TO STORE HAVING SOME PINE LIGHTS REPLACE, EXISTING PINE LIGHTS ARE VERY DIM AND YELLOW COMPARED TO NEW, MANAGER REQUEST N N TBA QUOTE TO REPLACE PINE LIGHTS AND DRIVERS
FRONT SWAROVSKI LOGO/SIGN SHOP FRONT FACING PROUDS 1 THE SWAN, V AND I IS ILLUMINATED HOWEVER THE REST OF THE SIGN IS VERY DIM N N TBA OBSERVATION. SIGN REQUIRES REPLACING
TEST AND TAG STORE 25 TEST AND TAG IN DATE, NEXT TEST REQUIRED 26/10/22 N N N OBSERVATION
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, note compliance date
Are there any repairs and additional works required?No
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE POWDER 2.5KG 29_04_22 10/2019 GREEN BOH Y
Next Test Due in 3 months29/10/2022
Site Status SelectorStore now fully compliant
Technician's NameNATHAN MCBAIN
Store Manager's NameNick -