Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateVIC
Date of Visit02/06/2017
Technician's NameJoe Chetcuti
Built Job Number23795
Swarovski Site in VICbourke_street_mall
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Main Board downstairs 7 y p
9 y p
11 y p
13 y p
8 y p
10 y p
12 y p
DB1 upstairs 3 y p
5 y p
7 y p
9 y p
11 y p
2 y p
4 y p
6 y p
8 y p
10 y p
12 y p
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
main board em 2 r y y y p
em 3 r y y y p
em 4 r y y y p
DB1 em 9 r y f y f failed to illuminate y n
em 10 r y y y p
em 11 r y y y p
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Main board ex1 y y y p
ex5 y y y p
DB1 ex 6 y y y p
ex 7 y y y p
ex 8 y y y p
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auNo
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
35w downlight globe womens toilet 1 failed to illuminate y n n
28w T5 globes out upstairs office 2 failed to illuminate y n n
emergency light #9 upstairs 1 failed to illuminate y n n
lights out in poster display selling area 4 faulty transformer y n n
switchboard legend for upstairs and downstairs not accurate upstairs and downstairs switchboard 2 no legend n n n Legend to be delivered to site
square m/h downlights selling area 2 missing glass n y n
square m/h downlight selling area 1 not working n y n
no emergency lighting floor plan on premises 1 no emergency lighting floor plan y n n
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?No
Next Test Due in 3 months02/09/2017
Site Status SelectorStore now fully compliant
Technician's NameJoe Chetcuti
Store Manager's NameHarrison Gage