Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
Report any failures and provide costing to rectify (where applicable)
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
db1
1
s
y
n
y
f
failed on battery, need sizzor to replace
n
n
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
db1
1
y
y
y
p
2
y
n
n
f
failed on battery
n
n
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au
Yes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?
No
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
em 1 failed
near registers
1
failed 90 min test
n
y
n
Need vertical lift, works must be done before stores in DFO open so you can drive vertical telescopic lift in and out with out pedestrians, 1 x surface mount fitting required
store room light
store room wall
1
exposed wiring, ohs concern
y
n
n
Completed
spot light
mounted to track lighting
1
failed to illuminate
n
y
n
Requires new 35w globe
1 x 400w high bay
near registers
1
failed to illuminate
n
y
n
Requires vertical lift and new fitting. Must be completed before trading hours of complex
20w globes out
under cabinets near registers
2
failed to illuminate
n
y
n
Requires two globes but possibly could be the transformers
mini opticle fibre spot lights
11 cases
11
failed to illuminate
n
y
n
Replacement of opticle fibre boxes
extention lead across floor
powering fridge in BOH
1
ohs concern
n
y
n
Install new gpo , tps x 15m, feed from switch
General Works Checklist
Inspect all furniture and fittings for visible damage
Inspect all walls, ceilings, skirtings and floors for visible damage
Inspect storefront, façade and store LED logo for correct operations and visible damage
Inspect roller shutter and doors for correct operations and visible damage
Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?
No
Next Test Due in 3 months
01/09/2017
Site Status Selector
Store now fully compliant
Technician's Name
joe chetcuti
Store Manager's Name
mana dakic
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.