| Which Company are you working for? | Built Electrical |
|---|
| Which Trade are you working for? | Electrical |
|---|
| State | SA |
|---|
| Date of Visit | 13/02/2018 |
|---|
| Technician's Name | Daniel Moio |
|---|
| Built Job Number | 28088 |
|---|
| Swarovski Site in SA | marion |
|---|
| Test Period | 12 Monthly (90 minutes) |
|---|
| RCD Details (12 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| Unlabeled |
01 |
Y |
29 |
20 |
P |
|
|
|
02 |
Y |
48 |
44 |
P |
|
|
|
03 |
Y |
30 |
20 |
P |
|
|
|
04 |
Y |
25 |
16 |
P |
|
|
|
06 |
Y |
26 |
19 |
P |
|
|
|
08 |
Y |
31 |
19 |
P |
|
|
|
10 |
Y |
25 |
16 |
P |
|
|
|
12 |
Y |
24 |
19 |
P |
|
|
|
14 |
Y |
24 |
16 |
P |
|
|
|
16 |
Y |
29 |
19 |
P |
|
|
|
18 |
Y |
29 |
18 |
P |
|
|
|
20 |
Y |
27 |
32 |
P |
|
|
|
22 |
Y |
51 |
42 |
P |
|
|
|
24 |
Y |
N/A |
N/A |
P |
|
|
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
- Report any failures and provide costing to rectify (where applicable)
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
01 |
R |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
01 |
Y |
Y |
Y |
P |
|
|
|
|
02 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.au | Yes |
|---|
| If Yes, please upload all copies of legends here... (Limit of 6 megabytes total) |  |
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Troffer Fluoro Lights |
Store Room |
4 |
Blown lamp |
Y |
N |
N |
|
| Downlight |
Shop Floor |
2 |
Blown lamp |
Y |
N |
N |
|
| Downlight |
Shop Floor |
1 |
Blown lamp replaced, suspected faulty ballast |
N |
Y |
TBA |
Quote to be sent for approval. |
| LED Cabinet Lights |
Various |
2 |
Not working (row of 9) |
N |
Y |
TBA |
Quote to be sent for approval. |
| Emergency Test Switch |
Switchboard |
1 |
None installed |
N |
Y |
TBA |
Quote to be sent for approval. |
|
|---|
| General Works Checklist | - Inspect all furniture and fittings for visible damage
- Inspect all walls, ceilings, skirtings and floors for visible damage
- Inspect storefront, façade and store LED logo for correct operations and visible damage
- Inspect roller shutter and doors for correct operations and visible damage
- Check fire extinguishers, update compliance tags/labels
|
|---|
| Are there any repairs and additional works required? | Yes |
|---|
| General List of Repairs and additional works required | | Defect Item |
Location of Item |
Details of Problem |
Repaired on Site |
Quote to be Sent |
Comments |
| Ceiling |
Near crystal hanger |
Crack in ceiling |
N |
N |
John, please confirm if repairs are required. |
| Lock |
Crystals |
Not locking |
N |
N |
John, please confirm if new locks will be required. |
| Fire Extinguisher |
Store Room |
Not compliant - expired |
N |
N |
John to arrange testing. |
|
|---|
| Fire Extinguisher Details | | Type (ABE Powder) |
Size (4.5kg) |
Last Test Date |
Manufacture Date |
Pressure Indicator (Green Zone) |
Location In Store |
Compliant (Y/N) |
| ABE |
2.5 |
03/12 |
05/2011 |
Y |
Store Room |
N |
|
|---|
| Next Test Due in 3 months | 13/08/2018 |
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Technician's Name | Danny Moio |
|---|
| Store Manager's Name | angela clarke |
|---|
| |
|---|
| |