Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateSA
Date of Visit13/02/2018
Technician's NameDaniel Moio
Built Job Number28088
Swarovski Site in SAmarion
Test Period12 Monthly (90 minutes)
RCD Details (12 Month)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Unlabeled 01 Y 29 20 P
02 Y 48 44 P
03 Y 30 20 P
04 Y 25 16 P
06 Y 26 19 P
08 Y 31 19 P
10 Y 25 16 P
12 Y 24 19 P
14 Y 24 16 P
16 Y 29 19 P
18 Y 29 18 P
20 Y 27 32 P
22 Y 51 42 P
24 Y N/A N/A P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
01 R Y Y Y P
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
01 Y Y Y P
02 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auYes
If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)If Yes, please upload all copies of legends here... (Limit of 6 megabytes total)
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Troffer Fluoro Lights Store Room 4 Blown lamp Y N N
Downlight Shop Floor 2 Blown lamp Y N N
Downlight Shop Floor 1 Blown lamp replaced, suspected faulty ballast N Y TBA Quote to be sent for approval.
LED Cabinet Lights Various 2 Not working (row of 9) N Y TBA Quote to be sent for approval.
Emergency Test Switch Switchboard 1 None installed N Y TBA Quote to be sent for approval.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
Ceiling Near crystal hanger Crack in ceiling N N John, please confirm if repairs are required.
Lock Crystals Not locking N N John, please confirm if new locks will be required.
Fire Extinguisher Store Room Not compliant - expired N N John to arrange testing.
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE 2.5 03/12 05/2011 Y Store Room N
Next Test Due in 3 months13/08/2018
Site Status SelectorStore now fully compliant
Technician's NameDanny Moio
Store Manager's Nameangela clarke