Which Company are you working for?Built Electrical
Which Trade are you working for?Electrical
StateWA
Date of Visit03/04/2018
Technician's NameAdam Hoes
Built Job Number28089
Swarovski in WAperth
Test Period12 Monthly (90 minutes)
RCD Details (12 Month)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 01 Y .13 .15 P
03 Y .16 ,17 P
05 Y .19 .21 P
07 Y .17 ,18 P
09 Y .11 .13 P
11 Y .09 .10 P
02 Y .02 ,04 P
04 Y .04 .05 P
06 Y .09 .11 P
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 or 120 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicatior functions correctly
  • Report any failures and provide costing to rectify (where applicable)
Timers
  • Check timers for correct operation and timing
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 02 R Y N Y F Failed 90 Min Test Y N
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 01 Y Y Y P
02 Y Y Y P
General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
Are there accurate switchboard legends within each switchboard? Please take a photo send with report to epm@builtelectrical.com.auNo
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
Are there any Warranty items needing to be repaired?No
ELECTRICAL LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency Light Shop floor - 02 1 Failed 90 Min Test Y N N
Switchboard Back of house 1 Not Compliant N Y TBA Quote to be sent for approval.
Switchboard Legend Switchboard 1 Does not exist N Y TBA Quote to be sent for approval.
General Works Checklist
  • Inspect all furniture and fittings for visible damage
  • Inspect all walls, ceilings, skirtings and floors for visible damage
  • Inspect storefront, façade and store LED logo for correct operations and visible damage
  • Inspect roller shutter and doors for correct operations and visible damage
  • Check fire extinguishers, update compliance tags/labels
Are there any repairs and additional works required?Yes
General List of Repairs and additional works required
Defect Item Location of Item Details of Problem Repaired on Site Quote to be Sent Comments
1 x 9 Spot Rail Summer Glam 1228166 Light not working N N John, please advise if repairs are required.
1 x 9 Spot Rail Cool Romance 1228166 Light not working N N John, please advise if repairs are required.
1 x 9 Spot Rail Timeless Elegance 1228166 Light not working N N John, please advise if repairs are required.
1 x 9 Spot Rail Crystal Creations 1228166 Light not working N N John, please advise if repairs are required.
1 x 5 Spot Rail Small Display 1228170 Light not working N N John, please advise if repairs are required.
1 x 5 Spot Rail Tall Display 1228170 Light not working N N John, please advise if repairs are required.
Fire Extinguisher Details
Type (ABE Powder) Size (4.5kg) Last Test Date Manufacture Date Pressure Indicator (Green Zone) Location In Store Compliant (Y/N)
ABE Powder 2.5kg 06/2017 09/2016 Green Zone Back of house N - requires testing
Next Test Due in 3 months03/07/2018
Site Status SelectorStore now fully compliant
Technician's NameAdam Hoes
Store Manager's Nameannie wang