State | NSW |
---|
Date of Visit | 24/08/2020 |
---|
Technician's Name | Stephen Parker |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50942 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | wagga_wagga |
---|
|
|
---|
Location Name | Wagga Wagga |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
14 |
Y |
.047 |
.048 |
P |
|
|
|
26 |
Y |
.076 |
.061 |
P |
|
|
|
30 |
Y |
.095 |
.056 |
P |
|
|
|
31 |
Y |
.034 |
.039 |
P |
|
|
|
32 |
Y |
.176 |
.030 |
P |
|
|
|
34 |
Y |
.082 |
.087 |
P |
|
|
|
36 |
Y |
.059 |
.072 |
P |
|
|
|
38 |
Y |
.071 |
.059 |
P |
|
|
|
40 |
Y |
.047 |
.046 |
P |
|
|
|
42 |
Y |
.106 |
.082 |
P |
|
|
|
44 |
Y |
.045 |
.045 |
P |
|
|
|
46 |
Y |
.042 |
.043 |
P |
|
|
|
48 |
Y |
.046 |
.049 |
P |
|
|
|
50 |
Y |
.052 |
.047 |
P |
|
|
DB2 |
1 |
Y |
.051 |
.048 |
P |
|
|
|
2 |
Y |
.042 |
.051 |
P |
|
|
|
3 |
Y |
.061 |
.070 |
P |
|
|
|
4 |
Y |
.078 |
.069 |
P |
|
|
|
5 |
Y |
.052 |
.056 |
P |
|
|
|
6 |
Y |
.058 |
.106 |
P |
|
|
|
7 |
Y |
.059 |
.054 |
P |
|
|
|
8 |
Y |
.077 |
.063 |
P |
|
|
|
9 |
Y |
.079 |
.064 |
P |
|
|
|
10 |
Y |
.039 |
.039 |
P |
|
|
|
11 |
Y |
.052 |
.055 |
P |
|
|
|
12 |
Y |
.060 |
.060 |
P |
|
|
|
13 |
Y |
.061 |
.058 |
P |
|
|
|
14 |
Y |
.056 |
.054 |
P |
|
|
|
15 |
Y |
.052 |
.051 |
P |
|
|
|
16 |
Y |
.062 |
.052 |
P |
|
|
|
18 |
Y |
.060 |
.062 |
P |
|
|
|
19 |
Y |
.052 |
.049 |
P |
|
|
|
20 |
Y |
.054 |
.058 |
P |
|
|
|
21 |
Y |
.053 |
.051 |
P |
|
|
|
22 |
Y |
.047 |
.053 |
P |
|
|
|
23 |
Y |
.048 |
.048 |
P |
|
|
|
24 |
Y |
.052 |
.048 |
P |
|
|
|
25 |
Y |
.051 |
.052 |
P |
|
|
|
26 |
Y |
.060 |
.061 |
P |
|
|
|
27 |
Y |
.053 |
.057 |
P |
|
|
|
28 |
Y |
.058 |
.062 |
P |
|
|
|
29 |
Y |
.055 |
.058 |
P |
|
|
|
37 |
Y |
.049 |
.054 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
N |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
1 |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
UFO LED Hibays - Store |
Y |
LED Fluro - Warehouse |
Y |
36W Fluro - Store Security |
Y |
Shop Fitters - Entrance |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
LED Batten Emergency Light |
10 - Shop floor |
1 |
Failed 90 Min Test |
Y |
N |
N |
Replaced with Dual Surface Mount Spitfire |
Twin Spot Emergency Light |
12 - Shop floor |
1 |
Failed 90 Min Test |
Y |
N |
N |
Replaced fitting, scissor lift required. |
Exit Light |
01 & 04 - Shop floor |
2 |
Failed 90 Min Test |
Y |
N |
N |
Replaced fittings. |
LED Batten |
Warehouse |
1 |
Broken & hanging |
Y |
N |
N |
Repaired. |
Exhaust Fan |
Men's Toilet |
1 |
Hanging |
Y |
N |
N |
Repaired. |
|
---|
Site Status Selector | Store now fully compliant |
---|