Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit07/10/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51794
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAclarkson

Location NameClarkson
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1 Y 027 035 P
DB 01 2 Y 008 018 P
DB 01 5 Y 028 018 P
DB 01 9 Y 010 020 P
DB 01 2 Y 038 038 P
DB 01 4 Y 039 048 P
DB 01 6 Y 011 021 P
DB 01 8 Y 019 038 P
DB 01 10 Y 019 038 P
DB 01 12 Y 019 038 P
DB 01 14 Y 008 018 P
DB 01 16 Y 013 023 P
DB 01 18 Y 008 018 P
DB 01 20 Y 011 021 P
DB 02 13 Y 026 036 P
DB 02 15 Y 027 037 P
DB 02 17 Y 044 045 P
DB 02 19 Y 049 043 P
DB 02 25 Y 028 038 P
DB 02 27 Y 031 042 P
DB 02 2 Y 044 043 P
DB 02 4 Y 047 046 P
DB 02 6 Y 047 048 P
DB 02 8 Y 038 038 P
DB 02 10 Y 044 043 P
DB 02 12 Y 058 058 P
DB 02 14 Y 037 036 P
DB 02 16 Y 032 036 P
DB 02 18 Y 040 035 P
DB 02 20 Y 042 041 P
DB 02 22 Y 039 039 P
DB 02 24 Y 054 054 P
DB 02 26 Y 039 039 P
MSB 31 Y 045 045 P
MSB 33 Y 044 047 P
MSB 35 Y 041 041 P
MSB 37 Y 045 047 P
MSB 39 Y 039 039 P
MSB 41 Y 049 032 P
MSB 43 Y 052 052 P
MSB 45 Y 041 047 P
MSB 14 Y 028 018 P
MSB 16 Y 039 039 P
MSB 18 Y 025 025 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 03 2 S -2 by 36w batten Y Y Y P
DB 03 3 S-2 by 36w batten Y Y Y P
DB 03 4 S-2 by 36w batten Y Y Y P
DB 03 5 S-2 by 36w batten Y Y Y P
DB 03 6 S-2 by 36w batten Y Y Y P
DB 03 8 S-2 by 36w batten Y Y Y P
DB 03 9 S-2 by 36w batten Y Y Y P
DB 03 10 R Y Y Y P
DB 03 11 S-2 by 36w batten Y N Y F FAILED TEST Y N
DB 03 22 R Y Y Y P
DB 03 23 R Y Y Y P
DB 03 25 S Y Y Y P
DB 03 26 S Y Y Y P
DB 03 27 S Y Y Y P
DB 03 28 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 03 1 Y Y Y P
DB 03 7 Y Y Y P
DB 03 12 Y N Y F FAILED TEST Y N
DB 03 13 Y Y Y P
DB 03 14 Y Y Y P
DB 03 15 Y Y Y P
DB 03 16 Y Y Y P
DB 03 17 Y Y Y P
DB 03 18 Y Y Y P
DB 03 19 Y Y Y P
DB 03 20 Y Y Y P
DB 03 21 Y Y Y P
DB 03 24 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED HIBAYS Y
LED DAVIS BATTEN Y
18W DEFUSED BATTEN Y
ROUND HANECO RECESSED LIGHT Y
WEATHER PROOF BATTEN Y
VANDAL LIGHTS Y
EXIT Y
SPIT FIRE EMERGENCY Y
SURFACE MOUNT EMERGENCY Y
SURFACE 1 BY 36W EMERGENCY BATTEN Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
HANECO LARGE DOWN LIGHT ENTRY X1 NOT ILLUMINATED HANECO Y CHARGE FOR LABOUR ONLY
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
MSB SWITCH BOARD BOH x1 DOOR LOCK/HANDLE Y N N OH&S
EXIT #12 BOH X1 BACK DOOR Y N N OH&S
DUAL SURFACE EMERGENCY #11 BOH X1 WAREHOUSE Y N N OH&S
PELMET LIGHTS HEATING & COOLING x2 16X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS FRIDGES x5 40X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS TV'S x6 48X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS SOUND BARS x2 16X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS SMART HOMES x2 16X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS GAMING x1 8X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS MONITORS x1 8X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS HEAD PHONES x1 8X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS WEARABLES x1 8X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS MOBILE PLANS x1 8X LED LINIKABLE BATTENS N Y TBA
PELMET LIGHTS ACCESSORIES BAY X1 8X LED LINKABLE BATTENS N Y TBA
PELMET LIGHTS DESKTOPS/COMPUTERS X1 8X LED LINKABLE BATTENS N Y TBA
FLOOD LIGHT LOADING DOCK x1 NEW INSTALL N Y TBA OUTSIDE LIGHTING
WEATHERPROOF BATTENS BACK OF HOUSE x2 NOT WORKING N Y TBA OUTSIDE LIGHTING
THE GOOD GUYS SIGN FRONT OF STORE x1 NOT WORKING N Y TBA
Site Status SelectorStore now fully compliant
Next Test Due in 6 months07/04/2020