Partner Name | Transit Electrical Pty Ltd |
---|
State | WA |
---|
Date of Visit | 07/10/2020 |
---|
Technician's Name | Adam Hoes |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51794 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in WA | clarkson |
---|
|
|
---|
Location Name | Clarkson |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB 01 |
1 |
Y |
027 |
035 |
P |
|
|
DB 01 |
2 |
Y |
008 |
018 |
P |
|
|
DB 01 |
5 |
Y |
028 |
018 |
P |
|
|
DB 01 |
9 |
Y |
010 |
020 |
P |
|
|
DB 01 |
2 |
Y |
038 |
038 |
P |
|
|
DB 01 |
4 |
Y |
039 |
048 |
P |
|
|
DB 01 |
6 |
Y |
011 |
021 |
P |
|
|
DB 01 |
8 |
Y |
019 |
038 |
P |
|
|
DB 01 |
10 |
Y |
019 |
038 |
P |
|
|
DB 01 |
12 |
Y |
019 |
038 |
P |
|
|
DB 01 |
14 |
Y |
008 |
018 |
P |
|
|
DB 01 |
16 |
Y |
013 |
023 |
P |
|
|
DB 01 |
18 |
Y |
008 |
018 |
P |
|
|
DB 01 |
20 |
Y |
011 |
021 |
P |
|
|
DB 02 |
13 |
Y |
026 |
036 |
P |
|
|
DB 02 |
15 |
Y |
027 |
037 |
P |
|
|
DB 02 |
17 |
Y |
044 |
045 |
P |
|
|
DB 02 |
19 |
Y |
049 |
043 |
P |
|
|
DB 02 |
25 |
Y |
028 |
038 |
P |
|
|
DB 02 |
27 |
Y |
031 |
042 |
P |
|
|
DB 02 |
2 |
Y |
044 |
043 |
P |
|
|
DB 02 |
4 |
Y |
047 |
046 |
P |
|
|
DB 02 |
6 |
Y |
047 |
048 |
P |
|
|
DB 02 |
8 |
Y |
038 |
038 |
P |
|
|
DB 02 |
10 |
Y |
044 |
043 |
P |
|
|
DB 02 |
12 |
Y |
058 |
058 |
P |
|
|
DB 02 |
14 |
Y |
037 |
036 |
P |
|
|
DB 02 |
16 |
Y |
032 |
036 |
P |
|
|
DB 02 |
18 |
Y |
040 |
035 |
P |
|
|
DB 02 |
20 |
Y |
042 |
041 |
P |
|
|
DB 02 |
22 |
Y |
039 |
039 |
P |
|
|
DB 02 |
24 |
Y |
054 |
054 |
P |
|
|
DB 02 |
26 |
Y |
039 |
039 |
P |
|
|
MSB |
31 |
Y |
045 |
045 |
P |
|
|
MSB |
33 |
Y |
044 |
047 |
P |
|
|
MSB |
35 |
Y |
041 |
041 |
P |
|
|
MSB |
37 |
Y |
045 |
047 |
P |
|
|
MSB |
39 |
Y |
039 |
039 |
P |
|
|
MSB |
41 |
Y |
049 |
032 |
P |
|
|
MSB |
43 |
Y |
052 |
052 |
P |
|
|
MSB |
45 |
Y |
041 |
047 |
P |
|
|
MSB |
14 |
Y |
028 |
018 |
P |
|
|
MSB |
16 |
Y |
039 |
039 |
P |
|
|
MSB |
18 |
Y |
025 |
025 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB 03 |
2 |
S -2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
3 |
S-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
4 |
S-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
5 |
S-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
6 |
S-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
8 |
S-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
9 |
S-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
10 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
11 |
S-2 by 36w batten |
Y |
N |
Y |
F |
FAILED TEST |
Y |
N |
DB 03 |
22 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
23 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
25 |
S |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
26 |
S |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
27 |
S |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
28 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB 03 |
1 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
7 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
12 |
Y |
N |
Y |
F |
FAILED TEST |
Y |
N |
DB 03 |
13 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
14 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
15 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
16 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
17 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
18 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
19 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
20 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
21 |
Y |
Y |
Y |
P |
|
|
|
DB 03 |
24 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
LED HIBAYS |
Y |
LED DAVIS BATTEN |
Y |
18W DEFUSED BATTEN |
Y |
ROUND HANECO RECESSED LIGHT |
Y |
WEATHER PROOF BATTEN |
Y |
VANDAL LIGHTS |
Y |
EXIT |
Y |
SPIT FIRE EMERGENCY |
Y |
SURFACE MOUNT EMERGENCY |
Y |
SURFACE 1 BY 36W EMERGENCY BATTEN |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
WARRANTY | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault/problem |
Manufacturer |
Part Number |
Repaired on Site |
Comments |
HANECO LARGE DOWN LIGHT |
ENTRY |
X1 |
NOT ILLUMINATED |
HANECO |
|
Y |
CHARGE FOR LABOUR ONLY |
|
---|
Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
MSB SWITCH BOARD |
BOH |
x1 |
DOOR LOCK/HANDLE |
Y |
N |
N |
OH&S |
EXIT #12 |
BOH |
X1 |
BACK DOOR |
Y |
N |
N |
OH&S |
DUAL SURFACE EMERGENCY #11 |
BOH |
X1 |
WAREHOUSE |
Y |
N |
N |
OH&S |
PELMET LIGHTS |
HEATING & COOLING |
x2 |
16X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
FRIDGES |
x5 |
40X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
TV'S |
x6 |
48X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
SOUND BARS |
x2 |
16X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
SMART HOMES |
x2 |
16X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
GAMING |
x1 |
8X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
MONITORS |
x1 |
8X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
HEAD PHONES |
x1 |
8X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
WEARABLES |
x1 |
8X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
MOBILE PLANS |
x1 |
8X LED LINIKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
ACCESSORIES BAY |
X1 |
8X LED LINKABLE BATTENS |
N |
Y |
TBA |
|
PELMET LIGHTS |
DESKTOPS/COMPUTERS |
X1 |
8X LED LINKABLE BATTENS |
N |
Y |
TBA |
|
FLOOD LIGHT |
LOADING DOCK |
x1 |
NEW INSTALL |
N |
Y |
TBA |
OUTSIDE LIGHTING |
WEATHERPROOF BATTENS |
BACK OF HOUSE |
x2 |
NOT WORKING |
N |
Y |
TBA |
OUTSIDE LIGHTING |
THE GOOD GUYS SIGN |
FRONT OF STORE |
x1 |
NOT WORKING |
N |
Y |
TBA |
|
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 07/04/2020 |
---|
| |
---|
| |