Carry out push button test and record the results below.
RCD Details (Biennial)
Distribution Board No.
Circuit No.
Push Button (YorN)
0 Degrees
180 Degrees
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DBU2
10
Y
25
19
P
20
Y
12
23
P
21
Y
26
18
P
Dbu3A
17
Y
28
18
P
Dbu3b
18
Y
23
2t
P
19
Y
44
45
P
21
Y
28
19
P
23
Y
38
39
P
Db05
1
Y
47
50
P
2
Y
44
44
P
3
Y
33
50
P
4
Y
69
69
P
5
Y
56
56
P
6
Y
44
95
P
7
Y
30
38
P
8
Y
44
45
P
9
Y
38
38
P
10
Y
49
48
P
11
Y
39
39
P
12
Y
49
39
P
13
Y
38
39
P
14
Y
40
40
P
15
Y
56
54
P
16
Y
47
50
P
17
Y
44
44
P
18
Y
56
95
P
27
Y
47
59
P
28
Y
44
44
P
29
Y
33
50
P
30
Y
45
40
P
31
Y
69
69
P
32
Y
56
56
P
33
Y
35
40
P
34
Y
30
38
P
35
Y
44
45
P
36
Y
38
38
P
37
Y
49
48
P
38
Y
44
45
P
39
Y
33
50
P
Dblg4
4
Y
26
17
P
24
Y
26
16
P
8
Y
28
19
P
16
Y
49
39
P
18
Y
29
39
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB4 & DB01
S2
R
Y
Y
Y
P
Ef3
S 4ft Fluoro
Y
Y
Y
P
S5
S
Y
Y
Y
P
Ef7
S 4ft Fluoro
Y
Y
Y
P
Ef8
S 4ft Fluoro
Y
Y
Y
P
Ef9
S 4ft Fluoro
Y
Y
Y
P
Ef11
S 4ft Fluoro
Y
Y
Y
P
S14
R
Y
Y
Y
P
S15
R
Y
Y
Y
P
S16
R
Y
Y
Y
P
S17
R
Y
Y
Y
P
S18
S
Y
Y
Y
P
S19
S
Y
Y
Y
P
S20
S
Y
Y
Y
P
EF21
S 4ft Fluoro
Y
Y
Y
P
EF22
S 4ft Fluoro
Y
Y
Y
P
EF25
S 4ft Fluoro
Y
Y
Y
P
EF26
S 4ft Fluoro
Y
Y
Y
P
EF27
S 4ft Fluoro
Y
Y
Y
P
EF28
S 4ft Fluoro
Y
Y
Y
P
EF30
S 4ft Fluoro
Y
Y
Y
P
S37
R
Y
Y
Y
P
S38
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB04 & DB01
1
Y
Y
Y
P
4
Y
Y
Y
P
6
Y
Y
Y
P
10
Y
Y
Y
P
12
Y
Y
Y
P
13
Y
Y
Y
P
23
Y
Y
Y
P
24
Y
Y
Y
P
29
Y
Y
Y
P
36
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
Fluoro High-bays 200W
Y
LED 4ft Fluoro 20W
Y
2ft Single Fluoro 840
Y
4ft Single Fluoro 840
Y
4ft Twin Fluoro 840
Y
4ft Twin LED Fluoro 18W
Y
4ft Single LED Fluoro 18W
Y
Shop Light Rectangle 38W
Y
LED Downlight 9W
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
LED Batten
Kitchen
1
Not illuminated
Y
N
N
Replaced fitting
Halogen Downlights
TV Area
27
27 not illuminated, 41 in area
Y
N
N
Replaced all 41 as it would not have looked suitable to replace only 27
DB-05
TV Area
1
The mains cable have exposed copper above the lug. This requires heat shrink. Also there is two 4 pole contactors that are hanging in the board. This could cause a hot joint.
Y
N
N
Repaired - suggest upgrade
DBu3a Switchboard
BOH Switchroom
1
Dbu3a missing main switch handle.
N
N
Y
New handle being sourced, will replace during next EPM.
Exit Light
Above Fire Door
1
Not illuminated as per Maintenance Request 1084
Y
N
N
Repaired
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
15/04/2020