Partner Name | Transit Electrical Pty Ltd |
---|
State | WA |
---|
Date of Visit | 14/10/2020 |
---|
Technician's Name | Adam Hoes |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51797 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in WA | mandurah |
---|
|
|
---|
Location Name | Mandurah |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB01 - General Light & Power |
1R |
Y |
028 |
038 |
P |
|
|
|
1W |
Y |
018 |
048 |
P |
|
|
|
1B |
Y |
018 |
038 |
P |
|
|
|
3R |
Y |
018 |
048 |
P |
|
|
|
3W |
Y |
028 |
048 |
P |
|
|
|
3B |
Y |
018 |
048 |
P |
|
|
|
5R |
Y |
028 |
036 |
P |
|
|
|
5W |
Y |
017 |
028 |
P |
|
|
|
5B |
Y |
026 |
040 |
P |
|
|
|
7R |
Y |
025 |
038 |
P |
|
|
|
7W |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
7B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
9R |
Blank |
Blank |
Blank |
Blank |
|
|
|
9W |
Blank |
Blank |
Blank |
Blank |
|
|
|
9B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
11R |
Y |
017 |
026 |
P |
|
|
|
11W |
Y |
018 |
028 |
P |
|
|
|
11B |
Y |
038 |
048 |
P |
|
|
|
13R |
Y |
018 |
048 |
P |
|
|
|
13W |
Y |
017 |
048 |
P |
|
|
|
13B |
Y |
028 |
038 |
P |
|
|
|
15R |
Y |
023 |
015 |
P |
|
|
|
15W |
Y |
030 |
020 |
P |
|
|
|
15B |
Y |
018 |
028 |
P |
|
|
|
17R |
Y |
028 |
048 |
P |
|
|
|
17W |
Y |
017 |
038 |
P |
|
|
|
17B |
Y |
028 |
048 |
P |
|
|
|
19R |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
19W |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
19B |
Y |
049 |
019 |
P |
|
|
|
R21-W23 |
Y |
022 |
009 |
P |
|
|
|
23 |
Blank |
Blank |
Blank |
Blank |
|
|
|
25 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
27 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
2R |
Y |
028 |
038 |
P |
|
|
|
2W |
Y |
018 |
048 |
P |
|
|
|
2B |
Y |
048 |
017 |
P |
|
|
|
4R |
Y |
048 |
018 |
P |
|
|
|
4W |
Y |
049 |
019 |
P |
|
|
|
4B |
Y |
029 |
019 |
P |
|
|
|
6R |
Y |
028 |
038 |
P |
|
|
|
6W |
Y |
052 |
022 |
P |
|
|
|
6B |
Y |
042 |
022 |
P |
|
|
|
8R |
Y |
050 |
021 |
P |
|
|
|
8W |
Blank |
Blank |
Blank |
Blank |
|
|
|
8B |
Blank |
Blank |
Blank |
Blank |
|
|
|
10R |
Y |
052 |
016 |
P |
|
|
|
10W |
Y |
044 |
017 |
P |
|
|
|
10B |
Y |
029 |
018 |
P |
|
|
|
12R |
Y |
044 |
017 |
P |
|
|
|
12W |
Y |
052 |
018 |
P |
|
|
|
12B |
Y |
044 |
018 |
P |
|
|
|
14R |
Y |
028 |
018 |
P |
|
|
|
14W |
Y |
048 |
018 |
P |
|
|
|
14B |
Y |
045 |
018 |
P |
|
|
|
16R |
Y |
028 |
038 |
P |
|
|
|
16W |
Y |
048 |
038 |
P |
|
|
|
16B |
Y |
Spare |
Spare |
P |
|
|
|
18R |
Y |
023 |
032 |
P |
|
|
|
18W |
Y |
028 |
021 |
P |
|
|
|
18B |
Y |
028 |
018 |
P |
|
|
|
20R |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
20W |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
20B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
22 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
24 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
26R |
Y |
028 |
019 |
P |
|
|
|
26W |
Blank |
Blank |
Blank |
Blank |
|
|
|
26B |
Blank |
Blank |
Blank |
Blank |
|
|
|
28R |
Blank |
Blank |
Blank |
Blank |
|
|
|
28W |
Blank |
Blank |
Blank |
Blank |
|
|
|
28B |
Blank |
Blank |
Blank |
Blank |
|
|
DB01 - Mechanical Services |
33 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
35 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
37 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
39R |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
39W |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
39B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
41R |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
41W |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
41B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
43R |
Blank |
Blank |
Blank |
Blank |
|
|
|
43W |
Blank |
Blank |
Blank |
Blank |
|
|
|
43B |
Blank |
Blank |
Blank |
Blank |
|
|
|
34 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
36 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
38 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
40R |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
40W |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
40B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
42R |
Blank |
Blank |
Blank |
Blank |
|
|
|
42W |
Blank |
Blank |
Blank |
Blank |
|
|
|
42B |
Blank |
Blank |
Blank |
Blank |
|
|
|
44R |
Blank |
Blank |
Blank |
Blank |
|
|
|
44W |
Blank |
Blank |
Blank |
Blank |
|
|
|
44B |
Blank |
Blank |
Blank |
Blank |
|
|
DB01 - Power |
45R |
Y |
025 |
016 |
P |
|
|
|
45W |
Y |
029 |
021 |
P |
|
|
|
45B |
Y |
031 |
028 |
P |
|
|
|
47R |
Y |
028 |
022 |
P |
|
|
|
47W |
Y |
048 |
018 |
P |
|
|
|
47B |
Y |
048 |
018 |
P |
|
|
|
49R |
Y |
048 |
038 |
P |
|
|
|
49W |
Y |
045 |
017 |
P |
|
|
|
49B |
Y |
028 |
018 |
P |
|
|
|
51R |
Blank |
Blank |
Blank |
Blank |
|
|
|
51W |
Blank |
Blank |
Blank |
Blank |
|
|
|
51B |
Blank |
Blank |
Blank |
Blank |
|
|
|
53R |
Blank |
Blank |
Blank |
Blank |
|
|
|
53W |
Blank |
Blank |
Blank |
Blank |
|
|
|
53B |
Blank |
Blank |
Blank |
Blank |
|
|
|
55R |
Blank |
Blank |
Blank |
Blank |
|
|
|
55W |
Blank |
Blank |
Blank |
Blank |
|
|
|
55B |
Blank |
Blank |
Blank |
Blank |
|
|
|
57R |
Blank |
Blank |
Blank |
Blank |
|
|
|
57W |
Blank |
Blank |
Blank |
Blank |
|
|
|
57B |
Blank |
Blank |
Blank |
Blank |
|
|
|
59R |
Blank |
Blank |
Blank |
Blank |
|
|
|
59W |
Blank |
Blank |
Blank |
Blank |
|
|
|
59B |
Blank |
Blank |
Blank |
Blank |
|
|
|
46R |
Y |
029 |
018 |
P |
|
|
|
46W |
Blank |
Blank |
Blank |
Blank |
|
|
|
46B |
Y |
029 |
021 |
P |
|
|
|
48R |
Y |
045 |
020 |
P |
|
|
|
48W |
Y |
049 |
019 |
P |
|
|
|
48B |
Y |
026 |
016 |
P |
|
|
|
50 R, W, B |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
52R |
Blank |
Blank |
Blank |
Blank |
|
|
|
52W |
Blank |
Blank |
Blank |
Blank |
|
|
|
52B |
Blank |
Blank |
Blank |
Blank |
|
|
|
54R |
Blank |
Blank |
Blank |
Blank |
|
|
|
54W |
Blank |
Blank |
Blank |
Blank |
|
|
|
54B |
Blank |
Blank |
Blank |
Blank |
|
|
|
56R |
Blank |
Blank |
Blank |
Blank |
|
|
|
56W |
Blank |
Blank |
Blank |
Blank |
|
|
|
56B |
Blank |
Blank |
Blank |
Blank |
|
|
|
58R |
Blank |
Blank |
Blank |
Blank |
|
|
|
58W |
Blank |
Blank |
Blank |
Blank |
|
|
|
58B |
Blank |
Blank |
Blank |
Blank |
|
|
|
60R |
Blank |
Blank |
Blank |
Blank |
|
|
|
60W |
Blank |
Blank |
Blank |
Blank |
|
|
|
60B |
Blank |
Blank |
Blank |
Blank |
|
|
DB02 - Front of store |
1 |
Y |
Spare |
Spare |
P |
|
|
|
3 |
Y |
025 |
016 |
P |
|
|
|
5 |
Y |
043 |
015 |
P |
|
|
|
7 |
Not RCD |
Not RCD |
Not RCD |
Not RCD |
|
|
|
9 |
Y |
044 |
016 |
P |
|
|
|
11 |
Y |
048 |
019 |
P |
|
|
|
13 |
Y |
044 |
033 |
P |
|
|
|
15 |
Y |
028 |
017 |
P |
|
|
|
17 |
Y |
047 |
037 |
P |
|
|
|
19 |
Y |
028 |
019 |
P |
|
|
|
21 |
Y |
048 |
018 |
P |
|
|
|
2 |
Y |
033 |
021 |
P |
|
|
|
4 |
Y |
028 |
038 |
P |
|
|
|
6 |
Y |
023 |
016 |
P |
|
|
|
8 |
Y |
026 |
016 |
P |
|
|
|
10 |
Y |
027 |
018 |
P |
|
|
|
12 |
Y |
027 |
015 |
P |
|
|
|
14 |
Y |
048 |
018 |
P |
|
|
|
16 |
Y |
031 |
022 |
P |
|
|
|
18 |
Y |
028 |
018 |
P |
|
|
|
20 |
Y |
050 |
040 |
P |
|
|
|
22 |
Y |
044 |
033 |
P |
|
|
|
24 |
Y |
024 |
015 |
P |
|
|
|
26 |
Y |
026 |
016 |
P |
|
|
|
28 |
Y |
026 |
036 |
P |
|
|
|
30 |
Blank |
Blank |
Blank |
Blank |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
db 01 |
2 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
4 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
6 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
7 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
9 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
10 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
13 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
14 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
16 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
17 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
18 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
19 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
20 |
R |
Y |
N |
Y |
F |
Failed Test |
Y |
N |
db 01 |
21 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
22 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
23 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
24 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
26 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
27 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
28 |
s-2 by 36w batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
31 |
1x 30w defused batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
33 |
1x 30w defused batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
35 |
1x 30w defused batten |
Y |
Y |
Y |
P |
|
|
|
db 01 |
36 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
37 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
38 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
39 |
R |
Y |
N |
N |
F |
Failed Test |
Y |
N |
db 01 |
40 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
41 |
R |
Y |
Y |
Y |
P |
|
|
|
db 01 |
42 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
db 01 |
1 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
3 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
5 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
8 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
11 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
12 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
15 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
25 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
29 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
30 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
32 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
34 |
Y |
Y |
Y |
P |
|
|
|
db 01 |
43 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
400W HIBAY |
Y |
400W LOW BAY |
Y |
400W LOW BAY DEFUSED |
Y |
12 VOLT HALOGEN DOWN LIGHTS |
Y |
LED DOWN LIGHTS SAL |
Y |
1 BY 36W DEFUSED BATTENS |
Y |
1 BY 30W DEFUSED BATTENS |
Y |
JUMBO EXIT |
Y |
2 BY PAR 38 SPOT |
Y |
1 BY 30W DEFUSED EMERGENCY BATTEN DUAL OPERATION |
Y |
OYSTER LIGHT |
Y |
LED OYSTER LIGHT |
Y |
150W ROUND MH SHOP LIGHT |
Y |
EXITS |
Y |
2 BY 36W DEFUSED EMERGENCY BATTEN |
Y |
SPIT FIRE EMERGENCY |
Y |
40W BATTEN |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
PELMET LIGHTS |
FRIDGES |
X5 |
NOT ILLUMINATED (40 LED LINKABLES REQUIRED) |
Y |
N |
N |
|
SIGN FAULT |
FRONT |
X1 |
DEAD SHORT |
N |
Y |
TBA |
|
LOWBAYS |
ENTRY |
X2 |
FITTINGS REQUIRED |
N |
Y |
TBA |
|
LOWBAYS |
REAR |
X9 |
FITTINGS REQUIRED |
N |
Y |
TBA |
|
BUNKER LIGHTS |
SIDE OF BUILDING |
X4 |
FITTINGS REQUIRED |
N |
Y |
TBA |
|
LED FLOOD LIGHTS |
OUTSIDE WALL |
X3 |
FITTINGS REQUIRED |
N |
Y |
TBA |
|
TIME CLOCK |
DISTRIBUTION BOARD |
X1 |
REQUIRED |
N |
Y |
TBA |
|
TOILET LIGHT |
18W 2PIN LAMP |
X1 |
NOT ILLUMINATED |
Y |
N |
N |
|
CLEANERS ROOMLIGHT |
18W 2 PIN LAMP |
X1 |
NOT ILLUMINATED |
Y |
N |
N |
|
FISHER AND PAYKEL |
FRIDGES |
X2 |
LAMPS |
Y |
N |
N |
|
SPITE FIRE EM |
EM #39 AND #20 |
X2 |
FAILED TEST |
Y |
N |
N |
OH&S |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 14/04/2021 |
---|
| |
---|
| |