Partner Name | Transit Electrical Pty Ltd |
---|
State | WA |
---|
Date of Visit | 15/10/2020 |
---|
Technician's Name | Adam Hoes |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51798 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in WA | rockingham |
---|
|
|
---|
Location Name | ROCKINGHAM |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
POWER CHASSIE |
1 |
Y |
061 |
031 |
P |
|
|
POWER CHASSIE |
1 |
Y |
FAIL |
FAIL |
F |
FAILED TEST |
N |
POWER CHASSIE |
3 |
Y |
029 |
032 |
P |
|
|
POWER CHASSIE |
3 |
Y |
039 |
038 |
P |
|
|
POWER CHASSIE |
3 |
Y |
056 |
060 |
P |
|
|
POWER CHASSIE |
5 |
Y |
047 |
042 |
P |
|
|
POWER CHASSIE |
5 |
Y |
050 |
050 |
P |
|
|
POWER CHASSIE |
5 |
Y |
022 |
022 |
P |
|
|
POWER CHASSIE |
7 |
Y |
025 |
034 |
P |
|
|
POWER CHASSIE |
7 |
Y |
FAIL |
FAIL |
F |
FAILED TEST |
N |
POWER CHASSIE |
7 |
Y |
FAIL |
FAIL |
F |
FAILED TEST |
N |
POWER CHASSIE |
9 |
Y |
039 |
039 |
P |
|
|
POWER CHASSIE |
9 |
Y |
044 |
079 |
P |
|
|
POWER CHASSIE |
9 |
Y |
FAIL |
FAIL |
F |
FAILED TEST |
N |
POWER CHASSIE |
11 |
Y |
SPARE |
SPARE |
P |
|
|
POWER CHASSIE |
11 |
Y |
053 |
053 |
P |
|
|
POWER CHASSIE |
13-15 RWB |
Y |
021 |
021 |
P |
|
|
POWER CHASSIE |
19-21 RWB |
Y |
020 |
020 |
P |
|
|
POWER CHASSIE |
2 |
Y |
030 |
030 |
P |
|
|
POWER CHASSIE |
2 |
Y |
071 |
053 |
P |
|
|
POWER CHASSIE |
2 |
Y |
039 |
039 |
P |
|
|
POWER CHASSIE |
4 |
Y |
039 |
040 |
P |
|
|
POWER CHASSIE |
4 |
Y |
050 |
051 |
P |
|
|
POWER CHASSIE |
4 |
Y |
FAIL |
FAIL |
F |
FAILED TEST |
N |
POWER CHASSIE |
6 |
Y |
035 |
034 |
P |
|
|
POWER CHASSIE |
6 |
Y |
029 |
039 |
P |
|
|
POWER CHASSIE |
8 |
Y |
049 |
050 |
P |
|
|
POWER CHASSIE |
8 |
Y |
043 |
046 |
P |
|
|
POWER CHASSIE |
8 |
Y |
047 |
047 |
P |
|
|
POWER CHASSIE |
8 |
Y |
SPARE |
SPARE |
P |
|
|
POWER CHASSIE |
10 |
Y |
SPARE |
SPARE |
P |
|
|
POWER CHASSIE |
10 |
Y |
045 |
045 |
P |
|
|
POWER CHASSIE |
10 |
Y |
046 |
049 |
P |
|
|
POWER CHASSIE |
12 |
Y |
048 |
049 |
P |
|
|
POWER CHASSIE |
16-18 RWB |
Y |
019 |
019 |
P |
|
|
POWER CHASSIE |
22-24 RWB |
Y |
031 |
021 |
P |
|
|
THE GOOD GUYS CHASSIE |
1 |
Y |
040 |
040 |
P |
|
|
THE GOOD GUYS CHASSIE |
3 |
Y |
039 |
039 |
P |
|
|
THE GOOD GUYS CHASSIE |
3 |
Y |
077 |
076 |
P |
|
|
THE GOOD GUYS CHASSIE |
3 |
Y |
047 |
047 |
P |
|
|
THE GOOD GUYS CHASSIE |
5 |
Y |
044 |
043 |
P |
|
|
THE GOOD GUYS CHASSIE |
5 |
Y |
051 |
051 |
P |
|
|
THE GOOD GUYS CHASSIE |
7 |
Y |
058 |
059 |
P |
|
|
THE GOOD GUYS CHASSIE |
7 |
Y |
039 |
048 |
P |
|
|
THE GOOD GUYS CHASSIE |
9 |
Y |
042 |
048 |
P |
|
|
THE GOOD GUYS CHASSIE |
9 |
Y |
030 |
032 |
P |
|
|
THE GOOD GUYS CHASSIE |
2 |
Y |
030 |
029 |
P |
|
|
THE GOOD GUYS CHASSIE |
2 |
Y |
039 |
039 |
P |
|
|
THE GOOD GUYS CHASSIE |
2 |
Y |
078 |
078 |
P |
|
|
THE GOOD GUYS CHASSIE |
4 |
Y |
082 |
085 |
P |
|
|
THE GOOD GUYS CHASSIE |
4 |
Y |
089 |
087 |
P |
|
|
THE GOOD GUYS CHASSIE |
4 |
Y |
FAIL |
FAIL |
F |
FAILED TEST |
N |
THE GOOD GUYS CHASSIE |
6 |
Y |
078 |
047 |
P |
|
|
THE GOOD GUYS CHASSIE |
6 |
Y |
039 |
039 |
P |
|
|
THE GOOD GUYS CHASSIE |
6 |
Y |
048 |
049 |
P |
|
|
DB 01 |
1 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
1 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
1 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
3 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
3 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
3 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
5 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
5 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
5 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
7 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
7 |
Y |
024 |
018 |
P |
|
|
DB 01 |
7 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
9 |
Y |
027 |
021 |
P |
|
|
DB 01 |
9 |
Y |
031 |
022 |
P |
|
|
DB 01 |
9 |
Y |
024 |
016 |
P |
|
|
DB 01 |
2 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
2 |
Y |
028 |
018 |
P |
|
|
DB 01 |
2 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
4 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
4 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
4 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
6 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
6 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
6 |
Y |
FAILED |
FAILED |
F |
FAILED TEST |
N |
DB 01 |
8 |
Y |
017 |
008 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB 02- lighting chassie |
8 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
9 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassieng chassie |
10 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
11 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
12 |
S 1 by 36w defused emergency batten |
Y |
N |
Y |
F |
BATTERY |
Y |
N |
DB 02- lighting chassie |
13 |
S 1 by 36w defused emergency batten |
Y |
N |
Y |
F |
BATTERY |
Y |
N |
DB 02- lighting chassie |
14 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
15 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
16 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
17 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
19 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
20 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
21 |
S 1 by 36w defused emergency batten |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
24 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
26 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
27 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
28 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
29 |
R |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
30 |
R |
Y |
N |
Y |
F |
BATTERY |
Y |
N |
DB 02- lighting chassie |
31 |
R |
Y |
N |
Y |
F |
BATTERY |
Y |
N |
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB 02- lighting chassie |
1 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
2 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
3 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
4 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
5 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
6 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
7 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
18 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
22 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
23 |
Y |
Y |
Y |
P |
|
|
|
DB 02- lighting chassie |
25 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
2 x 36w defused battens |
Y |
1 by 36w defused batten |
Y |
4 foot LED slimline batten |
Y |
400w mh hibay |
Y |
LED hibay |
Y |
Exit sign |
Y |
2 by 36w emergency batten |
Y |
1 by 36w emergency batten |
Y |
50w hallogen down light |
Y |
Emergency spit fire |
Y |
Oyster light |
Y |
2 by 28w wp battens |
Y |
LED flood light |
Y |
2 by 36w troffer lights |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
RCBO |
POWER CHASSIE |
B1,W7,B7,B9,B4 |
FAILED TEST TRIP TIME AND PUSH |
N |
N |
Y |
22/10/20 - QUOTE #2533 APPROVED BY HEAD OFFICE. WORKS IN PROGRESS |
RCBO |
DB 01 |
R1,W1,B1,R3,W3,B3,R5,W5,B5,R7,B7,W7, R2,W2,R4,W4,B4,R6,W6,B6 |
FAILED TEST |
N |
N |
Y |
22/10/20 - QUOTE #2533 APPROVED BY HEAD OFFICE. WORKS IN PROGRESS |
PELMET LIGHTS |
AUDIO SYSTEMS |
X1 |
NOT ILLUMINATED, REQUIRE 8 X LED LINKABLES |
N |
Y |
TBA |
|
PELMET LIGHTS |
ACCESSORIES |
X1 |
NOT ILLUMINATED, REQUIRE 8 X LED LINKABLES |
N |
Y |
TBA |
|
PELMET LIGHTS |
WALL MOUNTS |
X1 |
NOT ILLUMINATED, REQUIRE 8 X LED LINKABLES |
N |
Y |
TBA |
|
SURFACED MOUNT EMERGENCY |
EM 11 AND 12 |
X2 |
FAILED TEST |
Y |
N |
N |
OH&S |
RECESSED EM |
EM 30 AND 31 |
X2 |
FAILED TEST |
Y |
N |
N |
OH&S |
FISHER AND PAYKEL DISPLAY |
POWER ISSUE |
X1 |
LEADS UNPLUGGED |
Y |
N |
N |
POWER |
|
---|
Site Status Selector | Completed but with repairs required |
---|
Next Test Due in 6 months | 15/04/2021 |
---|
| |
---|
| |