Partner NameBass Hill Electrical Pty Ltd
StateNSW
Date of Visit18/10/2020
Technician's NameShane Hamilton
Which Company are you working for?Please Choose...
Sturdie Job Number50960
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWcasula

Location NameCasula
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db A 1 Y 29 40 P
3 Y 29 40 P
5 Y 29 39 P
7 Y 30 40 P
9 Y 29 40 P
11 Y 30 40 P
13 Y 30 40 P
15 Y 30 40 P
17 Y 29 40 P
19 Y 30 41 P
21 Y 30 40 P
23 Y 29 39 P
25 Y 30 40 P
2 Y 30 49 P
4 Y 29 40 P
6 Y 29 39 P
8 Y 28 35 P
10 Y 29 40 P
12 Y 29 40 P
14 Y 29 40 P
16 Y 30 40 P
18 Y 30 40 P
20 Y 29 39 P
22 Y 30 40 P
24 Y 30 40 P
26 Y 31 43 P
28 Y 30 40 P
30 Y 30 40 P
32 Y 30 40 P
34 Y 29 39 P
36 Y 39 49 P
38 Y 30 40 P
Db1 7 Y 29 40 P
11 Y 28 29 P
13 Y 29 40 P
15 Y 29 20 P
17 Y 28 40 P
49 Y 29 39 P
51 Y 28 40 P
53 Y 28 40 P
55 Y 29 39 P
57 Y 29 40 P
59 Y 28 20 P
61 Y 29 41 P
63 Y 29 40 P
65 Y 29 40 P
67 Y 30 40 P
69 Y 28 22 P
71 Y 28 20 P
8 Y 29 40 P
10 Y 29 40 P
12 Y 29 40 P
14 Y 28 39 P
16 Y 29 39 P
18 Y 28 40 P
50 Y 29 39 P
52 Y 29 39 P
54 Y 29 40 P
56 Y 28 20 P
58 Y 29 39 P
60 Y 28 38 P
62 Y 29 38 P
64 Y 30 40 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
T18 DB EM1 S Y Y Y P
T18 DB EM2 S Y Y Y P
T18 DB EM3 S Y Y Y P
T18 DB EM4 S Y Y Y P
T18 DB EM5 S Y Y Y P
T18 DB EM6 S Y Y Y P
T18 DB EM7 S Y Y Y P
T18 DB EM8 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
T18 DB EX1 Y Y Y P
T18 DB EX2 Y Y Y P
T18 DB EX3 Y Y Y P
T18 DB EX4 Y Y Y P
T18 DB EX5 Y Y Y P
T18 DB EX6 Y Y Y P
T18 DB EX7 Y Y Y P
T18 DB EX8 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi Bay Halo Globe Y
2 x 28W Fluoro Y
2 x 28W Caged Fluoro Y
1200mm LED Batten Y
LED Pelmet Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Jumbo Exit Light Various 2 EXIT diffuser instead of Running Man N N N As per Caitlin, wait until lights fail to address.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months19/04/2021