StateQLD
Date of Visit20/10/2020
Technician's NameScott Benson
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51836
EmailEmail hidden; Javascript is required.
The Good Guys Site in QLDtownsville

Location NameTownsville
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
C11 23 Y 29 39 P
24 Y 28 39 P
25 Y 36 46 P
26 Y 27 44 P
27 Y 26 39 P
28 Y 25 18 P
76 Y 30 20 P
78 Y 24 16 P
79 Y 26 19 P
80 Y 29 18 P
81 Y 34 27 P
82 Y 33 24 P
83 Y 26 18 P
84 Y 30 23 P
85 Y 24 15 P
86 Y 28 21 P
87 Y 24 16 P
88 - - - F Did not trip Y
89 Y 24 16 P
90 Y 35 26 P
91 Y 24 16 P
92 Y 28 18 P
93 Y 26 19 P
94 Y 28 16 P
97 Y 190 15 P
99 Y 90 21 P
100 Y 33 45 P
110 Y 24 16 P
DB C11A 6 Y 21 31 P
8 Y 22 17 P
9 Y 10 20 P
10 Y 48 33 P
11 Y 9 18 P
12 Y 8 18 P
13 Y 42 40 P
14 Y 14 21 P
15 Y 16 26 P
16 Y 17 25 P
17 Y 13 22 P
18 Y 9 18 P
19 Y 15 26 P
20 Y 8 21 P
21 Y 8 18 P
DB Kitchen 1 Y 30 33 P
2 Y 28 32 P
3 Y 28 33 P
4 Y 28 33 P
5 Y 29 32 P
6 Y 31 36 P
7 Y 30 32 P
8 Y 29 32 P
9 Y 42 32 P
10 Y 29 32 P
11 Y 42 32 P
12 Y 40 38 P
13 Y 85 35 P
14 Y 29 32 P
15 Y 30 32 P
16 Y 29 33 P
17 Y 30 33 P
18 Y 29 32 P
19 Y 29 32 P
20 Y 26 33 P
21 Y 28 33 P
22 Y 29 32 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 2 R Y Y Y P
MSB 4 R Y Y Y P
MSB 5 R Y Y Y P
MSB 7 S 2 X 36w Y Y Y P
MSB 8 S 2 X 36w Y Y Y P
MSB 11 S 2 X 36w Y Y Y P
MSB 12 S 2 X 36w Y Y Y P
MSB 13 S 2 X 36w Y Y Y P
MSB 15 S 2 X 36w Y Y Y P
MSB 16 S 2 X 36w Y Y Y P
MSB 17 S 2 X 36w Y Y Y P
MSB 18 S 2 X 36w Y Y Y P
MSB 19 S 2 X 36w Y Y Y P
MSB 20 S 2 X 36w Y Y Y P
MSB 21 S 2 X 36w Y Y Y P
MSB 22 S 2 X 36w Y Y Y P
MSB 23 S 2 X 36w Y Y Y P
DBC-11A 24 S 2 X 36w Y Y Y P
DBC-11A 25 S 2 X 36w Y Y Y P
DBC-11A 26 S 2 X 36w Y Y Y P
DBC-11A 27 S 2 X 36w Y Y Y P
DBC-11A 28 S 2 X 36w Y Y Y P
DBC-11A 30 S 2 X 36w Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 Y Y Y P
MSB 3 Y Y Y P
MSB 6 Y Y Y P
MSB 9 Y Y Y P
MSB 10 Y Y Y P
MSB 14 Y Y Y P
DBC-11A 29 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
2 X 28w BATTEN- DIFFUSED Y
FLUORO DISPLAY CASE LIGHT Y
LED HIGH BAY FITTING Y
LED STRIP LIGHT Y
LED DOWNLIGHTS IN KITCHEN DISPLAY Y
OYSTER FITTINGS 32w Y
OYSTER FITTINGS LED 18W Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
LED Highbay Ovens / Fridges 2 Not illuminated Davis BE000576 N To be replaced on warranty job
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
RCBO MSB 1 Failed trip test Y N N Replaced RCD
MSB MSB 3 Screws missing Y N N Replaced with new screws
Site Status SelectorStore now fully compliant
Next Test Due in 6 months15/03/2021