State | NSW |
---|
Date of Visit | 16/10/2020 |
---|
Technician's Name | Joel Bewley |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50963 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | tamworth |
---|
|
|
---|
Location Name | Tamworth |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
7 |
Y |
0.007 |
0.017 |
P |
|
|
|
8 |
Y |
0.001 |
0.008 |
P |
|
|
|
9 |
Y |
0.013 |
0.022 |
P |
|
|
|
10 |
Y |
0.018 |
0.015 |
P |
|
|
|
11 |
Y |
0.009 |
0.018 |
P |
|
|
|
12 |
Y |
0.01 |
0.025 |
P |
|
|
|
13 |
Y |
0.009 |
0.018 |
P |
|
|
|
14 |
Y |
0.014 |
0.024 |
P |
|
|
|
15 |
Y |
0.009 |
0.018 |
P |
|
|
|
17 |
Y |
0.014 |
0.024 |
P |
|
|
|
18 |
Y |
0.013 |
0.022 |
P |
|
|
|
19 |
Y |
0.009 |
0.015 |
P |
|
|
|
21 |
Y |
0.013 |
0.027 |
P |
|
|
|
23 |
Y |
0.010 |
0.002 |
P |
|
|
|
24 |
Y |
0.012 |
0.021 |
P |
|
|
|
25 |
Y |
0.023 |
0.027 |
P |
|
|
|
26 |
Y |
0.014 |
0.023 |
P |
|
|
|
33 |
Y |
0.008 |
0.018 |
P |
|
|
|
34 |
Y |
0.009 |
0.019 |
P |
|
|
|
35 |
Y |
0.008 |
0.019 |
P |
|
|
|
36 |
Y |
0.001 |
0.023 |
P |
|
|
|
37 |
Y |
0.007 |
0.017 |
P |
|
|
|
38 |
Y |
0.009 |
0.0019 |
P |
|
|
|
39 |
Y |
0.009 |
0.019 |
P |
|
|
|
40 |
Y |
0.0012 |
0.022 |
P |
|
|
|
43 |
Y |
0.009 |
0.018 |
P |
|
|
|
44 |
Y |
0.008 |
0.018 |
P |
|
|
|
45 |
Y |
0.002 |
0.003 |
P |
|
|
|
46 |
Y |
0.009 |
0.018 |
P |
|
|
|
47 |
Y |
0.028 |
0.003 |
P |
|
|
DB2 |
1 |
Y |
0.028 |
0.03 |
P |
|
|
|
2 |
Y |
0.039 |
0.038 |
P |
|
|
|
3 |
Y |
0.039 |
0.039 |
P |
|
|
|
4 |
Y |
0.039 |
0.038 |
P |
|
|
|
5 |
Y |
0.039 |
0.039 |
P |
|
|
|
6 |
Y |
0.029 |
0.028 |
P |
|
|
|
7 |
Y |
0.03 |
0.031 |
P |
|
|
|
8 |
Y |
0.029 |
0.028 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
N |
Y |
F |
Battery failed 90 minute test |
Y |
N |
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
N |
Y |
F |
Battery failed 90 minute test |
Y |
N |
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Y |
Y |
Y |
P |
|
|
|
|
19 |
Y |
Y |
Y |
P |
|
|
|
|
20 |
Y |
Y |
Y |
P |
|
|
|
|
21 |
Y |
Y |
Y |
P |
|
|
|
|
23 |
Y |
Y |
Y |
P |
|
|
|
|
24 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
LED Fluro 4FT Light x 33 |
Y |
UFO Hi Bay x 70 |
Y |
LED Downlights x 55 |
Y |
LED Rectangular Downlight x 4 |
Y |
LED Fluro 2FT Light x 9 |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
WARRANTY | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault/problem |
Manufacturer |
Part Number |
Repaired on Site |
Comments |
LED UFO hibay |
Shop floor |
5 |
Not illuminated |
Davis |
UFO150EA5K3B09 |
N |
To be replaced on warranty job |
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
12VD 6W LED Downlight |
TV room |
2 |
Not illuminated |
Y |
N |
N |
Replaced new transformer |
Emergency light #6 & #11 |
Shop floor |
2 |
Battery failed 90 minute test |
Y |
N |
N |
Replaced emergency lights |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 16/04/2021 |
---|
| |
---|
| |