StateVIC
Date of Visit28/10/2020
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51748
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICballarat

Location NameBallarat
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
SUB BOARD 1 09 Y 23 23 P
SUB BOARD 1 11 Y 33 33 P
SUB BOARD 1 12 Y 37 37 P
SUB BOARD 1 15 Y 19 19 P
SUB BOARD 1 17 Y 18 18 P
SUB BOARD 1 31 Y 32 32 P
SUB BOARD 1 32 Y 37 37 P
SUB BOARD 1 40 Y 18 19 P
SUB BOARD 1 42 Y 19 19 P
SUB BOARD 1 44 Y 19 19 P
SUB BOARD 1 46 Y 19 19 P
SUB BOARD 1 47 Y 19 20 P
SUB BOARD 1 48 Y 19 19 P
SUB BOARD 1 50 Y 32 35 P
SUB BOARD 1 54 Y 19 19 P
SUB BOARD 1A 01 Y 18 18 P
SUB BOARD 1A 04 Y 33 33 P
SUB BOARD 1A 05 Y 19 19 P
SUB BOARD 1A 07 Y 31 31 P
SUB BOARD 1A 10 Y 19 19 P
SUB BOARD 1A 13 Y 40 41 P
SUB BOARD 1A 16 Y 33 32 P
SUB BOARD 1A 22 Y 19 19 P
SUB BOARD 1A 27 Y 32 39 P
SUB BOARD 1A 29 Y 18 18 P
SUB BOARD 1A 31 Y 19 19 P
SUB BOARD 1A 32 Y 36 39 P
SUB BOARD 1A 33 Y 31 38 P
SUB BOARD 1A 34 Y 19 19 P
SUB BOARD 1A 35 Y 31 38 P
SUB BOARD 1A 36 Y 19 19 P
SUB BOARD 1A 37 Y 30 37 P
SUB BOARD 1A 38 Y 19 19 P
SUB BOARD 1A 39 Y 31 38 P
SUB BOARD 1A 40 Y 19 19 P
SUB BOARD 1A 41 Y 19 19 P
SUB BOARD 1A 43 Y 19 19 P
SUB BOARD 1A 44 Y 20 19 P
SUB BOARD 1A 45 Y 19 19 P
SUB BOARD 1A 46 Y 19 19 P
SUB BOARD 1A 48 Y 19 19 P
SUB BOARD 2 20 Y 19 19 P
SUB BOARD 2 24 Y 19 19 P
SUB BOARD 2 26 Y 19 19 P
SUB BOARD 2 28 Y 19 19 P
SUB BOARD 2 40 Y 19 19 P
SUB BOARD 2 42 Y 19 19 P
SUB BOARD 2 44 Y 19 18 P
SUB BOARD 2 46 Y 153 22 P
SUB BOARD 2 48 Y 18 18 P
SUB BOARD 2A 04 Y 32 32 P
SUB BOARD 2A 06 Y 39 35 P
SUB BOARD 2A 08 Y 32 32 P
SUB BOARD 2A 10 Y 34 37 P
SUB BOARD 2A 12 Y 19 19 P
SUB BOARD 2A 14 Y 29 37 P
SUB BOARD 2A 16 Y 29 37 P
SUB BOARD 2A 18 Y 30 38 P
SUB BOARD 2A 20 Y 32 41 P
SUB BOARD 2A 22 Y 19 19 P
SUB BOARD 2A 24 Y 19 19 P
SUB BOARD 2A 28 Y 19 19 P
SUB BOARD 2A 29 Y 43 38 P
SUB BOARD 2A 30 Y 19 19 P
SUB BOARD 2A 31 Y 32 33 P
SUB BOARD 2A 32 Y 19 19 P
SUB BOARD 2A 33 Y 31 30 P
SUB BOARD 2A 34 Y 32 31 P
SUB BOARD 2A 35 Y 32 33 P
SUB BOARD 2A 36 Y 19 19 P
SUB BOARD 2A 37 Y 33 31 P
SUB BOARD 2A 38 Y 19 19 P
SUB BOARD 2A 39 Y 32 33 P
SUB BOARD 2A 40 Y 19 19 P
SUB BOARD 2A 41 Y 32 32 P
SUB BOARD 2A 44 Y 19 19 P
SUB BOARD 2A 46 Y 19 19 P
SUB BOARD 2A 48 Y 19 19 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 R Y Y Y P
2 R Y Y Y P
3 R Y Y Y P
4 R Y Y Y P
5 R Y Y Y P
6 S Y N Y F Battery failed 90 minute test Y N
7 S Y N Y F Battery failed 90 minute test Y N
8 S Y N Y F Battery failed 90 minute test Y N
9 S Y N Y F Battery failed 90 minute test Y N
10 S Y N Y F Battery failed 90 minute test Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
DAVIS LED BATTEN 4K Y
HIGHBAY Y
TWIN LED TUBED BARE BATTENS Y
RECESSED EMERGENCY Y
SURFACE MOUNT EMERGENCY Y
EXIT LIGHTS Y
TWIN LED TUBED TROFFERS Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
CB04 Sub board 2A 1 RCBO tripping each day on start up N Y N Quote to be sent to Head Office
CB37 Sub board 2A 1 RCBO tripping each day on start up N Y N Quote to be sent to Head Office
Site folder Store 1 No site folder Y N N New folder sent to store
DB legends Sub board 1, 1A, 2, 2A 4 Legends required to be updated Y N N Installed updated legends
Hibay T.V area in front of TCL 1 Light was flashing N N N Hibay has intermittent fault. Will be replaced upon next audit if faulty
Mixed EM/EX & general lighting circuit, CB36 Sub board 2 1 circuit Mixed circuit with staff areas (kitchen/ toilets) circuit not through test unit N N N Chantelle advised this is a non issue
EM# 6 single 18W emergency batten Downstairs store room 1 Battery failed 90 minute test Y N N Replace emergency batten
EM# 7 36W non maintained emergency batten Downstairs store room 1 Battery failed 90 minute test Y N N Replace emergency batten
EM# 8 36W non maintained emergency batten Downstairs store room 1 Battery failed 90 minute test Y N N Replace emergency batten
Mixed EM/EX & general lighting circuit, CB34 Downstairs store room 1 Currently not through test unit/ mixed circuit N N N Chantelle advised this is a non issue
Recessed emergency light BOH upstairs old T.V area 2 Fitting not through test unit N N N Chantelle advised this is a non issue
Emergency test units Sub boards 2 Resets on test units not working will however time out N N N Currently no circuits through test unit above Sub Board 2A as a result of the mixed circuits above
Emergency lighting layout Store 1 Does not exist N N N Will be placed in site folder upon next visit
LED floodlight Front car park 1 Not illuminated Y N N Replaced LED floodlight
EM#9 & #10 single 36W non maintained emergency batten Apex of ceiling 2 Battery failed 90 minute test Y N N Replaced emergency batten
Site Status SelectorStore now fully compliant
Next Test Due in 6 months28/04/2021