Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit28/10/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51803
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAcannington

Location NameCannington
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1R Y 028 018 P
1W Y 038 018 P
1B Y 028 018 P
3R Y 048 038 P
3W Y 048 038 P
3B Y 038 038 P
5R Y 048 038 P
5W Y 048 038 P
5B Y 048 038 P
7R Y 050 038 P
7W Y 048 038 P
7B Y 048 038 P
9R Y 044 039 P
9W Y 051 041 P
9B Y 050 044 P
13R Y 023 015 P
13W Y 028 018 P
13B Y 024 037 P
15R Y 069 038 P
15B Y 048 037 P
17R Y 047 037 P
19W Y 049 038 P
19B Y 068 038 P
21B Y 031 041 P
2W Y 048 038 P
2B Y 048 038 P
4R Y 048 038 P
4W Y 048 038 P
4B Y 047 038 P
6R Y 048 038 P
6W Y 048 039 P
6B Y 048 038 P
18R Y 060 050 P
18W Y 054 044 P
18B Y 052 039 P
20R Y 029 020 P
20W Y 042 038 P
20B Y 047 038 P
22R Y 053 038 P
22W Y 049 038 P
22B Y 044 037 P
24R Y 048 038 P
DB 03 1 Y 038 029 P
3 Y 033 035 P
5 Y 029 033 P
7 Y 031 030 P
9 Y 031 038 P
11 Y 038 039 P
15 Y 031 029 P
21 Y 064 042 P
23 Y 039 037 P
25 Y 033 033 P
27 Y 038 038 P
29 Y 035 046 P
31 Y 039 047 P
33 Y 038 039 P
35 Y 029 032 P
37 Y 034 047 P
39 Y 031 046 P
41 Y 030 038 P
43 Y 033 030 P
45 Y 045 035 P
47 Y 030 030 P
8 Y 029 050 P
10 Y 038 029 P
12 Y 039 041 P
14 Y 046 042 P
16 Y 034 029 P
18 Y 029 042 P
20 Y 041 039 P
22 Y 029 035 P
24 Y 029 032 P
26 Y 029 029 P
28 Y 029 029 P
30 Y 050 042 P
32 Y 031 044 P
34 Y 040 043 P
36 Y 039 048 P
38 Y 031 030 P
40 Y 029 0303 P
42 Y 036 029 P
44 Y 055 047 P
46 Y 030 029 P
48 Y 031 031 P
50 Y 032 031 P
52 Y 035 031 P
54 Y 038 028 P
58 Y 029 036 P
60 Y 033 041 P
DB 04 - 2 1R Y 028 039 P
1W Y 028 018 P
1B Y 028 038 P
3R Y 028 018 P
3W Y 028 019 P
3B Y 028 018 P
5R Y 028 038 P
5W Y 028 018 P
5B Y 028 018 P
7R Y 039 039 P
7W Y 025 019 P
7B Y 025 020 P
9R Y 028 038 P
9W Y 035 025 P
2R Y 043 016 P
2W Y 028 018 P
2B Y 028 038 P
4R Y 029 038 P
4W Y 024 038 P
4B Y 028 038 P
6R Y 048 018 P
6W Y 028 018 P
6B Y 029 038 P
8R Y 024 047 P
8W Y 050 021 P
8B Y 029 020 P
10R Y 048 019 P
10W Y 028 018 P
10B Y 028 018 P
12R Y 028 038 P
12W Y 026 015 P
12B Y 028 019 P
DB 04 - 1 1 Y 050 038 P
3 Y 050 039 P
5 Y 057 047 P
7 Y 048 037 P
11 Y 028 038 P
13 Y 053 041 P
17 Y 048 038 P
19 Y 048 038 P
29 Y 049 038 P
43 Y 048 040 P
2 Y 047 040 P
4 Y 048 058 P
6 Y 048 045 P
8 Y 051 042 P
10 Y 048 038 P
12 Y 048 038 P
14 Y 026 015 P
22 Y 024 015 P
48 Y 049 039 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 04 - 1 2 R Y Y Y P
DB 04 - 1 5 R Y Y Y P
DB 04 - 1 6 R Y Y Y P
DB 04 - 1 7 R Y Y Y P
DB 01 8 S - Twin tube fluoro Y Y Y P
DB 04 - 1 11 R Y Y Y P
DB 01 13 S - Twin tube fluoro Y Y Y P
DB 01 19 S - Twin tube fluoro Y Y Y P
DB 01 20 S - Twin tube fluoro Y Y Y P
DB 01 24 S - Twin tube fluoro Y Y Y P
DB 01 25 S - Twin tube fluoro Y Y Y P
DB 01 30 R Y Y Y P
DB 01 31 R Y Y Y P
DB 01 32 R Y Y Y P
DB 01 33 R Y Y Y P
DB 01 34 R Y Y Y P
DB 01 36 S - Twin tube fluoro Y Y Y P
DB 01 37 S - Twin tube fluoro Y Y Y P
DB 01 38 S - Twin tube fluoro Y Y Y P
DB 03 41 S - Single fluoro Y Y Y P
DB 03 42 S - Single fluoro Y Y Y P
DB 03 45 R Y Y Y P
DB 03 46 R Y Y Y P
DB 03 48 R Y Y Y P
DB 03 49 R Y Y Y P
DB 03 50 R Y Y Y P
DB 03 51 S - Single fluoro Y Y Y P
DB 03 53 S - Single fluoro Y Y Y P
DB 03 54 S - Single fluoro Y Y Y P
DB 03 55 S - Single fluoro Y Y Y P
DB 03 56 S - Single fluoro Y Y Y P
DB 03 57 S - Single fluoro Y Y Y P
DB 03 58 S - Single fluoro Y Y Y P
DB 03 59 S- SINGLE FLUORO Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 04 - 1 1 Y Y Y P
DB 04 - 1 3 Y Y Y P
DB 04 - 1 4 Y Y Y P
DB 04 - 1 9 Y Y Y P
DB 04 - 1 10 Y Y Y P
DB 04 - 1 12 Y Y Y P
DB 01 14 Y Y Y P
DB 01 15 Y Y Y P
DB 01 16 Y Y Y P
DB 01 17 Y Y Y P
DB 01 18 Y Y Y P
DB 01 21 Y Y Y P
DB 01 22 Y Y Y P
DB 01 23 Y Y Y P
DB 01 26 Y Y Y P
DB 01 27 Y Y Y P
DB 01 28 Y Y Y P
DB 01 29 Y Y Y P
DB 01 35 Y Y Y P
DB 01 39 Y Y Y P
DB 01 40 Y Y Y P
DB 03 43 Y Y Y P
DB 03 44 Y Y Y P
DB 03 47 Y Y Y P
DB 03 52 Y Y Y P
DB 03 60 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
400w Lowbay Y
400w Hibays Y
LED Downlights Y
2 by 36w Emergency battens - Defused Y
Emergency Spitfire Y
Exits Y
Par 38 Spots Y
Par 38 Recessed lights Y
150w MH Shoplights Y
1 by 36w Defused battens Y
1 by 36w Emergency Defused battens Y
2 by 18w Defused battens Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
PELMET LIGHT MONITORS 1 FAULTY FITTING N Y TBA
PELMET LIGHT WEARABLES 1 FAULTY FITTING N Y TBA
PELMET LIGHT HEADPHONES 1 FAULTY FITTING N Y TBA
PELMET LIGHT SMART HOME 1 FAULTY FITTING N Y TBA
PELMET LIGHT SOUND BARS 2 FAULTY FITTING N Y TBA
PELMET LIGHT TV 1 FAULTY FITTING N Y TBA
PELMET LIGHT FRIDGES X2 FAULTY FITTING N Y TBA
Site Status SelectorStore now fully compliant
Next Test Due in 6 months28/04/2020