Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit29/10/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51805
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAosborne_park

Location NameOsborne Park
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB T1 11 Y 047 048 P
11 Y 049 040 P
11 Y 048 050 P
13 Y 048 048 P
13 Y 048 048 P
13 Y 056 056 P
15 Y 062 061 P
15 Y 048 048 P
15 Y 039 062 P
17 Y 039 049 P
17 Y 108 070 P
17 Y 051 051 P
19 Y 051 051 P
12 Y 070 051 P
12 Y 041 041 P
12 Y 057 069 P
14 Y 061 043 P
14 Y 069 069 P
14 Y 053 053 P
16 Y 048 048 P
16 Y 030 030 P
16 Y 051 051 P
18 Y 043 042 P
18 Y 063 053 P
18 Y 063 062 P
20 Y 063 062 P
DB 02 1 Y 071 027 P
1 Y 008 017 P
1 Y 015 024 P
5 Y 012 023 P
5 Y 008 018 P
5 Y 007 017 P
7 Y 008 018 P
7 Y 015 015 P
7 Y 016 017 P
2 Y 009 019 P
2 Y 008 017 P
2 Y 007 018 P
4 Y 011 021 P
4 Y 030 020 P
4 Y 012 021 P
6 Y 008 018 P
6 Y 028 018 P
6 Y 009 018 P
8 Y 007 017 P
8 Y 007 017 P
8 Y 009 018 P
10 Y 010 019 P
10 Y 008 018 P
10 Y 028 018 P
12 Y 008 017 P
12 Y 029 018 P
12 Y 008 018 P
SUB BOARD 2 3 Y 041 051 P
3 Y 041 022 P
5 Y 023 032 P
5 Y 012 022 P
9 Y 007 017 P
13 Y 008 007 P
13 Y 016 018 P
2 Y 012 021 P
2 Y 028 018 P
2 Y 008 017 P
4 Y 009 018 P
4 Y 028 018 P
4 Y 027 017 P
6 Y 010 020 P
6 Y 009 018 P
6 Y 007 017 P
8 Y 007 017 P
8 Y 008 017 P
8 Y 010 019 P
10 Y 017 017 P
10 Y 008 018 P
14 Y 027 017 P
14 Y 028 018 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DBT1 2 R Y Y Y P
3 R Y Y Y P
4 R Y N Y F Battery Y N
5 S - Twin batten type Y Y Y P
6 S - Twin batten type Y Y Y P
7 S - Twin batten type Y Y Y P
9 S - Twin batten type Y Y Y P
10 S - Twin batten type Y Y Y P
11 S - Twin batten type Y Y Y P
12 S - Twin batten type Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 S - Twin batten type Y Y Y P
17 S - Twin batten type Y Y Y P
19 R Y Y Y P
20 S - Twin batten type Y Y Y P
21 S - Twin batten type Y Y Y P
22 S - Twin batten type Y Y Y P
25 S - Twin batten type Y Y Y P
26 S - Twin batten type Y Y Y P
27 S - Twin batten type Y Y Y P
30 R Y Y Y P
32 S - Twin batten type Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DBT1 1 Y Y Y P
8 Y Y Y P
11 Y Y Y P
13 Y Y Y P
18 Y Y Y P
23 Y Y Y P
24 Y Y Y P
28 Y Y Y P
29 Y Y Y P
31 Y Y Y P
33 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
400W Hi-Bay Lights Y
16y 18W Lights Y
Oyster Lights Y
16y 36W Diffused Battens Y
LED Down Lights Y
Exit Lights Y
Spitfire Emergency Lights Y
26y 36W Emergency Battens Diffused Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
4 foot weather proof batten Front entry x1 Not illuminated Y N N Scissor lift was required
Recessed emergency #04 Shop floor x1 Failed test Y N N OH&S
Site Status SelectorStore now fully compliant
Next Test Due in 6 months29/04/2021