StateVIC
Date of Visit29/10/2020
Technician's NameAnthony Zammit
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51750
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICbrighton_extension

Location NameBrighton Extension
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
EDB4 4 Y 18 28 P
EDB4 6 Y 39 32 P
EDB4 8 Y 19 28 P
EDB4 10 Y 60 50 P
EDB4 12 Y 20 30 P
EDB4 14 Y 20 30 P
EDB4 16 Y 26 17 P
EDB4 18 Y 17 26 P
EDB4 19 Y 18 26 P
EDB4 20 Y 18 26 P
EDB4 21 Y 18 27 P
EDB4 22 Y 19 29 P
EDB4 23 Y 20 23 P
EDB4 24 Y 20 30 P
EDB4 25 Y 16 24 P
EDB4 26 Y 20 25 P
EDB4 27 Y 18 30 P
EDB4 28 Y 19 29 P
EDB4 29 Y 21 31 P
EDB4 30 Y 18 27 P
EDB4 31 Y 53 60 P
EDB4 32 Y 18 29 P
EDB4 33 Y 18 28 P
EDB4 34 Y 18 28 P
EDB4 35 Y 18 26 P
EDB4 36 Y 17 27 P
EDB4 37 Y 17 26 P
EDB4 38 Y 18 28 P
EDB4 39 Y 15 24 P
EDB4 40 Y 15 23 P
EDB4 41 Y 16 24 P
EDB4 42 Y 35 27 P
EDB4 43 Y 17 26 P
EDB4 44 Y 42 31 P
EDB4 45 Y 28 19 P
EDB4 46 Y 23 32 P
EDB4 47 Y 17 23 P
EDB4 48 Y 24 23 P
EDB4 50 Y 27 44 P
EDB4 51 Y 20 28 P
EDB4 52 Y 21 31 P
EDB4 53 Y 18 27 P
EDB4 55 Y 17 26 P
EDB4 56 Y 18 26 P
EDB4 57 Y 18 28 P
EDB4 58 Y 28 18 P
EDB4 59 Y 39 50 P
EDB4 60 Y 28 18 P
DB1 4 Y 17 25 P
DB1 6 Y 18 27 P
DB1 8 Y 17 25 P
DB1 9 Y 18 27 P
DB1 10 Y 18 28 P
DB1 11 Y 18 28 P
DB1 12 Y 19 28 P
DB1 13 Y 17 26 P
DB1 14 Y 20 28 P
DB1 15 Y 18 28 P
DB1 16 Y 18 28 P
DB1 17 Y 16 27 P
DB1 18 Y 40 25 P
DB1 19 Y 16 24 P
DB1 20 Y 18 28 P
DB1 21 Y 30 17 P
DB1 22 Y 18 27 P
DB1 23 Y 21 31 P
DB1 25 Y 18 27 P
DB1 27 Y 18 27 P
DB1 29 Y 18 24 P
DB1 31 Y 18 24 P
DB1 33 Y 17 24 P
DB1 35 Y 19 31 P
DB1 37 Y 18 28 P
EDB3 35 Y 32 41 P
EDB3 37 Y 38 32 P
EDB3 40 Y 27 17 P
EDB5 2 Y 27 21 P
EDB5 4 Y 33 33 P
EDB5 7 Y 28 21 P
EDB5 8 Y 27 22 P
EDB5 9 Y 28 21 P
EDB5 10 Y 27 21 P
EDB5 11 Y 27 19 P
EDB5 12 Y 27 21 P
EDB5 13 Y 27 22 P
EDB5 14 Y 30 22 P
EDB5 16 Y 27 22 P
EDB5 17 Y 27 21 P
EDB5 19 Y 27 21 P
EDB5 22 Y 30 32 P
EDB5 24 Y 32 34 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 Extension 1 R Y Y Y P
2 R Y Y Y P
3 R Y Y Y P
4 R Y Y Y P
5 R Y Y Y P
6 R Y Y Y P
7 R Y Y Y P
8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
11 R Y Y Y P
12 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 Extension 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
T5 Double Fluorescent Lights Y
Single 36W Fluorescent Lights Y
70mm Downlights Y
Exit Lights Y
Emergency Lights Y
LED Troffer Y
Recessed 3-Way Downlight Y
Recessed 2-Way Downlight Y
90mm LED Downlight Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
3-Way Downlight Upstairs Office 3 Failed to Illuminate N Y Has been previously quoted. Please advise if you would like this re-quoted.
2-Way Downlight Upstairs Office 3 Failed to Illuminate N Y Has been previously quoted. Please advise if you would like this re-quoted.
3-Way Downlight Above Staircase 2 Failed to Illuminate N Y Has been previously quoted. Please advise if you would like this re-quoted.
Track Light Side of store 10 Failed to Illuminate Y N N Replaced with 10 new track lights
150mm LED downlight Behind registers 1 Failed to Illuminate Y N N Replaced 4 downlights. 1 light behind counter was faulty and other 3 on the way out.
90mm LED downlight TV zone 43 Failed to Illuminate N Y Please advise if you would like this quoted.
Circuit 59 EDB4 1 Circuit keeps tripping N Y Has been previously quoted. Please advise if you would like this re-quoted.
LED Troffer Above LG TV Display 2 Failed to Illuminate Y N N
90mm LED Downlight Entrance 1 Failed to Illuminate Y N N
LED Troffer TV Bulk Stack 1 Failed to Illuminate Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months29/04/2021