StateVIC
Date of Visit30/10/2020
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51752
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICbrighton_warehouse

Location NameBrighton Warehouse
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB01 05 Y 30 32 P
DB01 06 Y 29 32 P
DB01 08 Y 31 32 P
DB01 14 Y 48 37 P
DB02 15 Y 18 18 P
DB03 01 Y 29 19 P
DB03 02 Y 19 9 P
DB03 03 Y 30 19 P
DB03 11 Y 30 38 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
N/A 1 R Y Y Y P
2 R Y Y Y P
3 R Y Y Y P
4 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
N/A 5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
SURFACE MOUNTED TRIPLE LIGHT FITTING Y
SINGLE 36W BARE BATTEN Y
DOUBLE 36W BARE BATTEN Y
SINGLE 18W BARE BATTEN Y
LED HI-BAY Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
NO TEST FACILITY/MIXED CIRCUIT SOUTH SIDE OF WARE HOUSE DB02 CB10 1 NO TEST FACILITY INSTALLED/MIXED LIGHTING CIRCUIT (LUNCHROOM TOILETS)/ CIRCUIT NOT AN RCD N Y Y QUOTE TO BE SENT FOR APPROVAL
NO RCDS INSTALLED IN DB2 DB2 SOUTH SIDE TBC NO RCDS INSTALLED, NO LEGEND ONSITE N Y Y QUOTE TO BE SENT FOR APPROVAL
NO DB LEGEND DB1/DB3 NORTH SIDE , DB2 SOUTH SIDE 3 NO LEGENDS INSTALLED N Y Y QUOTE TO BE SENT FOR APPROVAL
TRI 28W/840 TUBED TROFFER SOUTH SIDE AISLE T/AISLE R 2 FAILED TO ILLUMINATE N Y Y QUOTE TO BE SENT FOR APPROVAL
TRI 28W/840 TUBED TROFFER NORTH SIDE AISLE P/ AISLE O/ AISLE M/AISLE L/ AISLE K 9 FAILED TO ILLUMINATE N Y Y QUOTE TO BE SENT FOR APPROVAL
SINGLE 18W/840 BARE BATTEN NORTH SIDE FEMALE TOILET 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
SINGLE T8 15W LED TUBED BARE BATTEN SOUTH SIDE LUNCHROOM 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
SINGLE 18W/840 BARE BATTEN SOUTH SIDE FEMALE TOILET 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
SINGLE 18W/840 BARE BATTEN SOUTH SIDE MALE TOILET 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
Site Status SelectorCompleted but with repairs required
Next Test Due in 6 months30/04/2021