Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit05/11/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51807
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAjoondalup

Location NameJoondalup
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1R Y 027 019 P
1W Y 028 019 P
1B Y 024 016 P
3R Y 027 015 P
3W Y 047 017 P
3B Y 043 016 P
5R Y 028 017 P
5W Y 024 015 P
5B Y 028 017 P
7R Y 023 015 P
7W Y 024 016 P
7B Y 024 017 P
9R Y 041 030 P
9W Y 027 016 P
9B Y 026 017 P
11R Y 023 017 P
11W Y 024 015 P
11B Y 023 018 P
13R Y 048 017 P
13W Y 048 017 P
13B Y 027 017 P
15R Y 023 018 P
15W Y 023 015 P
15B Y 048 018 P
17R Y 028 018 P
17W Y 028 019 P
17B Y 026 017 P
19R Y 069 018 P
19W Not RCD Not RCD Not RCD P
19B Not RCD Not Rcd Not RCD P
21R Y 028 020 P
21W Y 026 018 P
21B Y 030 019 P
23R Not RCD Not RCD Not RCD P
23W Y 024 016 P
23B Y 037 041 P
25R, W, B Not RCD Not RCD Not RCD P
27R Not RCD Not RCD Not RCD P
27W Blank Blank Blank P
27B Blank Blank Blank P
29R Blank Blank Blank P
29W Blank Blank Blank P
29B Blank Blank Blank P
31R Blank Blank Blank P
31W Blank Blank Blank P
31B Blank Blank Blank P
2R Y 054 015 P
2W Y 026 015 P
2B Y 029 019 P
4R Y 029 019 P
4W Y 028 021 P
4B Y 026 016 P
6R Y 028 017 P
6W Y 029 019 P
6B Y 028 017 P
8R Y 024 015 P
8W Y 026 018 P
8B Y 028 018 P
10R Y 024 016 P
10W Y 027 018 P
10B Y 043 017 P
12R Y 023 017 P
12W Y 027 017 P
12B Y 027 018 P
14R Y 023 018 P
14W Y 027 017 P
14B Y 027 019 P
16R Y 027 017 P
16W Y 028 018 P
16B Y 048 018 P
18R Y 043 016 P
18W Y 031 022 P
18B Y 030 021 P
20R Y 028 019 P
20W Y 025 017 P
20B Y 047 019 P
22R Y 025 034 P
22W Y 025 018 P
22B Y 025 017 P
24R Y 020 015 P
24W Y 044 015 P
24B Y 028 038 P
26R Y 048 020 P
26W Blank Blank Blank P
26B Blank Blank Blank P
28R Blank Blank Blank P
28W Blank Blank Blank P
28B Blank Blank Blank P
30R Blank Blank Blank P
30W Blank Blank Blank P
30B Blank Blank Blank P
Mechanical 1 Not RCD Not RCD Not RCD P
3 Not RCD Not RCD Not RCD P
5 Not RCD Not RCD Not RCD P
7 Not RCD Not RCD Not RCD P
9 Not RCD Not RCD Not RCD P
11 Not RCD Not RCD Not RCD P
13-17 Not RCD Not RCD Not RCD P
19-23 Not RCD Not RCD Not RCD P
25-29 Not RCD Not RCD Not RCD P
31-35 Not RCD Not RCD Not RCD P
37 Y 028 018 P
39 Y 028 018 P
41 Y 026 027 P
43 Y 028 018 P
45 Not RCD Not RCD Not RCD P
47 Not RCD Not RCD Not RCD P
49 Not RCD Not RCD Not RCD P
51 Not RCD Not RCD Not RCD P
53 Not RCD Not RCD Not RCD P
55 Not RCD Not RCD Not RCD P
57 Not RCD Not RCD Not RCD P
59 Not RCD Not RCD Not RCD P
2 Not RCD Not RCD Not RCD P
4 Not RCD Not RCD Not RCD P
6 Not RCD Not RCD Not RCD P
8 Not RCD Not RCD Not RCD P
10 Not RCD Not RCD Not RCD P
12 Not RCD Not RCD Not RCD P
14 Not RCD Not RCD Not RCD P
16 Not RCD Not RCD Not RCD P
18 Not RCD Not RCD Not RCD P
20 Not RCD Not RCD Not RCD P
22 Not RCD Not RCD Not RCD P
24 Not RCD Not RCD Not RCD P
26 Not RCD Not RCD Not RCD P
28 Not RCD Not RCD Not RCD P
30 Not RCD Not RCD Not RCD P
32 Not RCD Not RCD Not RCD P
34 Not RCD Not RCD Not RCD P
36 Not RCD Not RCD Not RCD P
38 Not RCD Not RCD Not RCD P
40 Not RCD Not RCD Not RCD P
42 Not RCD Not RCD Not RCD P
44 Not RCD Not RCD Not RCD P
46 Not RCD Not RCD Not RCD P
48 Not RCD Not RCD Not RCD P
50 Not RCD Not RCD Not RCD P
52 Not RCD Not RCD Not RCD P
54 Not RCD Not RCD Not RCD P
56 Not RCD Not RCD Not RCD P
58 Not RCD Not RCD Not RCD P
60 Not RCD Not RCD Not RCD P
Sub board 1R Not RCD Not RCD Not RCD P
1W Y 048 017 P
1B Y 048 018 P
3R Y 028 018 P
4R Y 029 020 P
4W Y 048 018 P
4B Y 028 018 P
6R Y 027 018 P
6W Y 028 020 P
6B Y 028 017 P
8R Y 043 016 P
8W Y 027 018 P
8B Y 027 018 P
10R Y 028 018 P
10W Y 028 018 P
10B Y 026 018 P
12R Y 024 015 P
12W Y 024 015 P
12B Y 025 017 P
14R Blank Blank Blank P
14W Blank Blank Blank P
14B Blank Blank Blank P
16R Blank Blank Blank P
16W Blank Blank Blank P
16B Blank Blank Blank P
3W Y 048 017 P
3B Y 048 018 P
5R Y 028 018 P
5W Y 028 018 P
5B Y 043 016 P
7R Y 028 022 P
7W Not RCD Not RCD Not RCD P
7B Y 028 018 P
9R Y 031 031 P
9W Blank Blank Blank P
9B Blank Blank Blank P
11R Blank Blank Blank P
11W Blank Blank Blank P
11B Blank Blank Blank P
13R Blank Blank Blank P
13W Blank Blank Blank P
13B Blank Blank Blank P
15R Blank Blank Blank P
15W Blank Blank Blank P
15B Blank Blank Blank P
2R Not RCD Not RCD Not RCD P
2W Y 026 017 P
2B Y 052 016 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 2 S-2 by 28w batten Y Y Y P
3 S-2 by 28w batten Y Y Y P
4 S-2 by 28w batten Y Y Y P
5 S-2 by 28w batten Y Y Y P
6 S-2 by 28w batten Y Y Y P
7 S-2 by 28w batten Y Y Y P
8 S-2 by 28w batten Y Y Y P
9 S-2 by 28w batten Y Y Y P
12 R Y Y Y P
13 R Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 R Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
19 R Y Y Y P
20 R Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
Sub board 1 26 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Sub board 1 1 Y Y Y P
10 Y Y Y P
11 Y Y Y P
21 Y Y Y P
24 Y Y Y P
25 Y Y Y P
29 Y Y Y P
30 Y Y Y P
31 Y Y Y P
32 Y Y Y P
33 Y Y Y P
34 Y Y Y P
35 Y Y Y P
36 Y Y Y P
37 Y Y Y P
38 Y Y Y P
39 Y Y Y P
40 Y Y Y P
41 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Jumbo exit Y
400w defused low bay Y
Exit Y
2 by 28w defused emergency batten Y
1 by 28w defused batten Y
2 by 28w defused batten Y
LED down light Y
LED rectangular shop light Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
LED Hibay Hair Care X1 Dimmed DAVIS Y Scissor lift was required (not covered under warranty)
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Front sign Front and rear X2 Not powered or illuminated N N N Other contractor is sorting
Pelmet lights Mobile plan X1 Not illuminated - 8x linkables required N Y TBA
Pelmet lights Accessories X1 Not illuminated - 8x linkables required N Y TBA
Pelmet lights Wearables X1 Not illuminated - 8x linkables required N Y TBA
Pelmet lights Gaming X1 Not illuminated - 8x linkables required N Y TBA
Pelmet lights Smart Home X2 Not illuminated - 16x linkables required N Y TBA
Pelmet lights Audio Systems X1 Not illuminated - 8x linkables required N Y TBA
Pelmet lights Wall Brackets X1 Not illuminated - 8x linkables required N Y TBA
Site Status SelectorStore now fully compliant
Next Test Due in 6 months05/05/2021