Partner Name | Transit Electrical Pty Ltd |
---|
State | WA |
---|
Date of Visit | 05/11/2020 |
---|
Technician's Name | Adam Hoes |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51807 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in WA | joondalup |
---|
|
|
---|
Location Name | Joondalup |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB 01 |
1R |
Y |
027 |
019 |
P |
|
|
|
1W |
Y |
028 |
019 |
P |
|
|
|
1B |
Y |
024 |
016 |
P |
|
|
|
3R |
Y |
027 |
015 |
P |
|
|
|
3W |
Y |
047 |
017 |
P |
|
|
|
3B |
Y |
043 |
016 |
P |
|
|
|
5R |
Y |
028 |
017 |
P |
|
|
|
5W |
Y |
024 |
015 |
P |
|
|
|
5B |
Y |
028 |
017 |
P |
|
|
|
7R |
Y |
023 |
015 |
P |
|
|
|
7W |
Y |
024 |
016 |
P |
|
|
|
7B |
Y |
024 |
017 |
P |
|
|
|
9R |
Y |
041 |
030 |
P |
|
|
|
9W |
Y |
027 |
016 |
P |
|
|
|
9B |
Y |
026 |
017 |
P |
|
|
|
11R |
Y |
023 |
017 |
P |
|
|
|
11W |
Y |
024 |
015 |
P |
|
|
|
11B |
Y |
023 |
018 |
P |
|
|
|
13R |
Y |
048 |
017 |
P |
|
|
|
13W |
Y |
048 |
017 |
P |
|
|
|
13B |
Y |
027 |
017 |
P |
|
|
|
15R |
Y |
023 |
018 |
P |
|
|
|
15W |
Y |
023 |
015 |
P |
|
|
|
15B |
Y |
048 |
018 |
P |
|
|
|
17R |
Y |
028 |
018 |
P |
|
|
|
17W |
Y |
028 |
019 |
P |
|
|
|
17B |
Y |
026 |
017 |
P |
|
|
|
19R |
Y |
069 |
018 |
P |
|
|
|
19W |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
19B |
Not RCD |
Not Rcd |
Not RCD |
P |
|
|
|
21R |
Y |
028 |
020 |
P |
|
|
|
21W |
Y |
026 |
018 |
P |
|
|
|
21B |
Y |
030 |
019 |
P |
|
|
|
23R |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
23W |
Y |
024 |
016 |
P |
|
|
|
23B |
Y |
037 |
041 |
P |
|
|
|
25R, W, B |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
27R |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
27W |
Blank |
Blank |
Blank |
P |
|
|
|
27B |
Blank |
Blank |
Blank |
P |
|
|
|
29R |
Blank |
Blank |
Blank |
P |
|
|
|
29W |
Blank |
Blank |
Blank |
P |
|
|
|
29B |
Blank |
Blank |
Blank |
P |
|
|
|
31R |
Blank |
Blank |
Blank |
P |
|
|
|
31W |
Blank |
Blank |
Blank |
P |
|
|
|
31B |
Blank |
Blank |
Blank |
P |
|
|
|
2R |
Y |
054 |
015 |
P |
|
|
|
2W |
Y |
026 |
015 |
P |
|
|
|
2B |
Y |
029 |
019 |
P |
|
|
|
4R |
Y |
029 |
019 |
P |
|
|
|
4W |
Y |
028 |
021 |
P |
|
|
|
4B |
Y |
026 |
016 |
P |
|
|
|
6R |
Y |
028 |
017 |
P |
|
|
|
6W |
Y |
029 |
019 |
P |
|
|
|
6B |
Y |
028 |
017 |
P |
|
|
|
8R |
Y |
024 |
015 |
P |
|
|
|
8W |
Y |
026 |
018 |
P |
|
|
|
8B |
Y |
028 |
018 |
P |
|
|
|
10R |
Y |
024 |
016 |
P |
|
|
|
10W |
Y |
027 |
018 |
P |
|
|
|
10B |
Y |
043 |
017 |
P |
|
|
|
12R |
Y |
023 |
017 |
P |
|
|
|
12W |
Y |
027 |
017 |
P |
|
|
|
12B |
Y |
027 |
018 |
P |
|
|
|
14R |
Y |
023 |
018 |
P |
|
|
|
14W |
Y |
027 |
017 |
P |
|
|
|
14B |
Y |
027 |
019 |
P |
|
|
|
16R |
Y |
027 |
017 |
P |
|
|
|
16W |
Y |
028 |
018 |
P |
|
|
|
16B |
Y |
048 |
018 |
P |
|
|
|
18R |
Y |
043 |
016 |
P |
|
|
|
18W |
Y |
031 |
022 |
P |
|
|
|
18B |
Y |
030 |
021 |
P |
|
|
|
20R |
Y |
028 |
019 |
P |
|
|
|
20W |
Y |
025 |
017 |
P |
|
|
|
20B |
Y |
047 |
019 |
P |
|
|
|
22R |
Y |
025 |
034 |
P |
|
|
|
22W |
Y |
025 |
018 |
P |
|
|
|
22B |
Y |
025 |
017 |
P |
|
|
|
24R |
Y |
020 |
015 |
P |
|
|
|
24W |
Y |
044 |
015 |
P |
|
|
|
24B |
Y |
028 |
038 |
P |
|
|
|
26R |
Y |
048 |
020 |
P |
|
|
|
26W |
Blank |
Blank |
Blank |
P |
|
|
|
26B |
Blank |
Blank |
Blank |
P |
|
|
|
28R |
Blank |
Blank |
Blank |
P |
|
|
|
28W |
Blank |
Blank |
Blank |
P |
|
|
|
28B |
Blank |
Blank |
Blank |
P |
|
|
|
30R |
Blank |
Blank |
Blank |
P |
|
|
|
30W |
Blank |
Blank |
Blank |
P |
|
|
|
30B |
Blank |
Blank |
Blank |
P |
|
|
Mechanical |
1 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
3 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
5 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
7 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
9 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
11 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
13-17 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
19-23 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
25-29 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
31-35 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
37 |
Y |
028 |
018 |
P |
|
|
|
39 |
Y |
028 |
018 |
P |
|
|
|
41 |
Y |
026 |
027 |
P |
|
|
|
43 |
Y |
028 |
018 |
P |
|
|
|
45 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
47 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
49 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
51 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
53 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
55 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
57 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
59 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
2 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
4 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
6 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
8 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
10 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
12 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
14 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
16 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
18 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
20 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
22 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
24 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
26 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
28 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
30 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
32 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
34 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
36 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
38 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
40 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
42 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
44 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
46 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
48 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
50 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
52 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
54 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
56 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
58 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
60 |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
Sub board |
1R |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
1W |
Y |
048 |
017 |
P |
|
|
|
1B |
Y |
048 |
018 |
P |
|
|
|
3R |
Y |
028 |
018 |
P |
|
|
|
4R |
Y |
029 |
020 |
P |
|
|
|
4W |
Y |
048 |
018 |
P |
|
|
|
4B |
Y |
028 |
018 |
P |
|
|
|
6R |
Y |
027 |
018 |
P |
|
|
|
6W |
Y |
028 |
020 |
P |
|
|
|
6B |
Y |
028 |
017 |
P |
|
|
|
8R |
Y |
043 |
016 |
P |
|
|
|
8W |
Y |
027 |
018 |
P |
|
|
|
8B |
Y |
027 |
018 |
P |
|
|
|
10R |
Y |
028 |
018 |
P |
|
|
|
10W |
Y |
028 |
018 |
P |
|
|
|
10B |
Y |
026 |
018 |
P |
|
|
|
12R |
Y |
024 |
015 |
P |
|
|
|
12W |
Y |
024 |
015 |
P |
|
|
|
12B |
Y |
025 |
017 |
P |
|
|
|
14R |
Blank |
Blank |
Blank |
P |
|
|
|
14W |
Blank |
Blank |
Blank |
P |
|
|
|
14B |
Blank |
Blank |
Blank |
P |
|
|
|
16R |
Blank |
Blank |
Blank |
P |
|
|
|
16W |
Blank |
Blank |
Blank |
P |
|
|
|
16B |
Blank |
Blank |
Blank |
P |
|
|
|
3W |
Y |
048 |
017 |
P |
|
|
|
3B |
Y |
048 |
018 |
P |
|
|
|
5R |
Y |
028 |
018 |
P |
|
|
|
5W |
Y |
028 |
018 |
P |
|
|
|
5B |
Y |
043 |
016 |
P |
|
|
|
7R |
Y |
028 |
022 |
P |
|
|
|
7W |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
7B |
Y |
028 |
018 |
P |
|
|
|
9R |
Y |
031 |
031 |
P |
|
|
|
9W |
Blank |
Blank |
Blank |
P |
|
|
|
9B |
Blank |
Blank |
Blank |
P |
|
|
|
11R |
Blank |
Blank |
Blank |
P |
|
|
|
11W |
Blank |
Blank |
Blank |
P |
|
|
|
11B |
Blank |
Blank |
Blank |
P |
|
|
|
13R |
Blank |
Blank |
Blank |
P |
|
|
|
13W |
Blank |
Blank |
Blank |
P |
|
|
|
13B |
Blank |
Blank |
Blank |
P |
|
|
|
15R |
Blank |
Blank |
Blank |
P |
|
|
|
15W |
Blank |
Blank |
Blank |
P |
|
|
|
15B |
Blank |
Blank |
Blank |
P |
|
|
|
2R |
Not RCD |
Not RCD |
Not RCD |
P |
|
|
|
2W |
Y |
026 |
017 |
P |
|
|
|
2B |
Y |
052 |
016 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB 01 |
2 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S-2 by 28w batten |
Y |
Y |
Y |
P |
|
|
|
|
12 |
R |
Y |
Y |
Y |
P |
|
|
|
|
13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
14 |
R |
Y |
Y |
Y |
P |
|
|
|
|
15 |
R |
Y |
Y |
Y |
P |
|
|
|
|
16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
17 |
R |
Y |
Y |
Y |
P |
|
|
|
|
18 |
R |
Y |
Y |
Y |
P |
|
|
|
|
19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
Sub board 1 |
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
Sub board 1 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
21 |
Y |
Y |
Y |
P |
|
|
|
|
24 |
Y |
Y |
Y |
P |
|
|
|
|
25 |
Y |
Y |
Y |
P |
|
|
|
|
29 |
Y |
Y |
Y |
P |
|
|
|
|
30 |
Y |
Y |
Y |
P |
|
|
|
|
31 |
Y |
Y |
Y |
P |
|
|
|
|
32 |
Y |
Y |
Y |
P |
|
|
|
|
33 |
Y |
Y |
Y |
P |
|
|
|
|
34 |
Y |
Y |
Y |
P |
|
|
|
|
35 |
Y |
Y |
Y |
P |
|
|
|
|
36 |
Y |
Y |
Y |
P |
|
|
|
|
37 |
Y |
Y |
Y |
P |
|
|
|
|
38 |
Y |
Y |
Y |
P |
|
|
|
|
39 |
Y |
Y |
Y |
P |
|
|
|
|
40 |
Y |
Y |
Y |
P |
|
|
|
|
41 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Jumbo exit |
Y |
400w defused low bay |
Y |
Exit |
Y |
2 by 28w defused emergency batten |
Y |
1 by 28w defused batten |
Y |
2 by 28w defused batten |
Y |
LED down light |
Y |
LED rectangular shop light |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
WARRANTY | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault/problem |
Manufacturer |
Part Number |
Repaired on Site |
Comments |
LED Hibay |
Hair Care |
X1 |
Dimmed |
DAVIS |
|
Y |
Scissor lift was required (not covered under warranty) |
|
---|
Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
Front sign |
Front and rear |
X2 |
Not powered or illuminated |
N |
N |
N |
Other contractor is sorting |
Pelmet lights |
Mobile plan |
X1 |
Not illuminated - 8x linkables required |
N |
Y |
TBA |
|
Pelmet lights |
Accessories |
X1 |
Not illuminated - 8x linkables required |
N |
Y |
TBA |
|
Pelmet lights |
Wearables |
X1 |
Not illuminated - 8x linkables required |
N |
Y |
TBA |
|
Pelmet lights |
Gaming |
X1 |
Not illuminated - 8x linkables required |
N |
Y |
TBA |
|
Pelmet lights |
Smart Home |
X2 |
Not illuminated - 16x linkables required |
N |
Y |
TBA |
|
Pelmet lights |
Audio Systems |
X1 |
Not illuminated - 8x linkables required |
N |
Y |
TBA |
|
Pelmet lights |
Wall Brackets |
X1 |
Not illuminated - 8x linkables required |
N |
Y |
TBA |
|
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 05/05/2021 |
---|
| |
---|
| |